Troubleshooting
Tips save t ime a nd money!
Review
the chart below f irst and y ou may n ot need t ocall for s ervice.
Maintenance
and Service
• You may hear a pinging noise caused by water being picked up and thrown by the slinger fan against the
condenser on rainy days or when the humidity is high. This design feature helps remove moisture and
improve efficiency.
• You may hear the thermostat click when the compressor cycles on and off.
• Water will collect in the base pan during high humidity or on rainy days. The water may overflow and drip
from the outdoor side of the unit.
• The fan may run even when the compressor does not.
dut_<_
Fan motor
will not run.
• Check voltage
at outlet. Correct
if none.
• Check voltage
to rotary
switch. If none, check
power
supply
cord. Replace
cord if circuit
is open.
• Check switch
continuity.
Refer to wiring
diagram
for
terminal
identification.
Replace
switch
if defective.
• Connect
wire. Refer to wiring
diagram
for terminal
identification.
Repair or replace
loose terminal.
Replace
if not within +10%
of manufacturer's
rating.
Replace
if shorted,
open, or damaged.
• Fan blade hitting shroud
or cross flow fan hitting
scroll. Realign
assembly.
• Units using slinger
ring condenser
fans must have 1/4
to s/16 inch clearance
to the base.
If it is hitting the
base, shim up the bottom
of the fan motor with
mounting
screw(s).
• Check fan motor bearings;
if motor shaft will not
rotate, replace
the motor.
Fan motor runs
intermittently
Owner's Manual
23