Maintenance Clearances - LG Multi V ARNU073M2A4 Installation Manual

Ducted indoor units
Hide thumbs Also See for Multi V ARNU073M2A4:
Table of Contents

Advertisement

Figure 18: High-Static Ducted (B8) Indoor Unit Maintenance
Clearances.
A2
Figure 20: Mid-Static Ducted (MA/M1/M2/M3) and High-Static Ducted
(M2/M3) Indoor Unit Maintenance Clearances.
A3
A2
Table 19: Minimum Maintenance Clearances (in.).
Chassis Code
Location
Convertible Mid-Static, Mid-Static, and High-Static Ducted Indoor Units
MA
Right End
M1
Right End
M2
Right End
M3
Right End
B8
Right End
Low-Static Ducted Indoor Units
L1
Right End
L2
Right End
L3
Right End
*Does not apply when the ceiling surface below can be removed.
GENERAL INSTALLATION GUIDELINES
C2
C1
A1
C2
C1
A1
Control Panel Access
C1
C2
8
8
8
8
8
8
8
8
12
14
10
12
10
12
10
12
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 19: Low-Static Ducted (L1/L2/L3) Indoor Unit Maintenance
Clearances.
C3
A3
A3
A2
Figure 21: Mid-Static Ducted (MA/M1/M2/M3) and High-Static Ducted
(B8/M2/M3) Indoor Unit Maintenance Clearances.
Top view
[Unit: inch]
C3
C3
Location
10
Bottom
10
Bottom
10
Bottom
12
Bottom
18
Bottom
Bottom
8
Bottom
8
Bottom
8

Maintenance Clearances

A1
Inspection hole
>23-5/8 x >23-5/8
Air inlet vents
Control box
>10
>39-3/8
Air outlet
vents
Front
Major Maintenance Access
A1
A2
40
32
40
32
50
28
50
28
62
28
30
25
38
25
46
25
C2 C1
C3
>23-5/8
A3*
12
12
12
15
19
8
8
8
39