Step 5
3 Wire System
The followingprocedure should be used forcopper (#1)
or aluminum (#2) wire connection:
Power Cord Installation--insert
screws through
power cord terminals so that the screws pass through
connector block terminals and engage nuts. Tighten
screws securely.
POWER CORD
RING TERMINAL
CONNECTOR
BLOCK
TERMINAL
POWER
CORD
MOVABLE
NUT
Cable Direct Installation--Clamp
bare wires between
the connector block terminals and movable nuts with
screws tightened securely.
SCREW
CONNECTOR
BLOCK
TERMINAL
WIRE_
.
FLEXIBLE
1. Copper Wiring
Connect the neutral or grounded wireofthe supplycir-
cuit to the neutral terminal of the connector block,
located in the center. The power leads must be con-
nected to the outside brass terminals.
NEUTRAL
TERMINAL
GROUNDING STRAP
(GROUNDED TO RANGE)
WARNING:
CONNECTOR
BLOCK
IS APPROVED
FOR COPPER WIRE CONNECTION
ONLY,
2. Aluminum
Wiring
A. Connect length of copper building wire to range ter-
minal block.
B. Splice copper wires to aluminum wiring using
special connectors designed and U.L. approved for
joining copper to aluminum, and follow the connector
manufacturer's recommended procedure closely.
NOTE: Wire used, location and enclosure of splices,
etc., must conform to good wiring practice and local
codes.
Step 6
4 Wire System
Special GroundingInstructions
WARNING: Frame grounded to neutral of appliance
through a link.If used in a MOBILE HOME or if LOCAL
CODES do not permit grounding through the neutral:
1. Disconnect the link from neutral.
2. Use grounding terminal or lead to ground unit in
accordance with local codes.
3. Connect neutral terminal or lead to branch circuit in
usual manner.
(If the appliance
is to be connected
by means of acord
set, use 4-conductor
cord for this purpose.)
CONNECTOR
BLOCK
4th GROUNDING LEAD
GROUND
LUG
7