Power Connection; All Units - Frigidaire FRA106HT10 Use & Care Manual

Packaged terminal air conditioner
Table of Contents

Advertisement

ELECTRICAL
SHOCK HAZARD
Failure to follow this warning
could result in personal
injury or death and/or
property damage.
DO NOT alter cord or plug or use an extension cord.
POWER
CONNECTION
OPTIONS
Amperage
and voltage
of the PTAC and branch
circuit
must match according
to local cord.
If the unit is to be hard wired, an accessory
hard wire kit must be ordered.
ALL UNITS
Wire Size
Use recommended
wire size given in Table 1 and install a single branch circuit.
All wiring
must comply with
local and national
codes. All units are designed
to operate
on ONE single
branch circuit,
NOTE: Use copper conductors
only.
Table
Z--SUGGESTED
BRANCH
CIRCUIT
WIRE
SIZES _<
NAMEPLATE
AMPS
AWG WIRE
SIZE +
7.0 to 12
14
12.1 to 16
12
16,1 to 24
10
LEGEND
AWG ---American
Wire Gauge
Single circuit from main box.
+ Based on copper wire at 60 °C temperature
rating.
Grounding
For safety and protection,
the unit is grounded
through
the service cord plug or through
separate
ground
wire provided
on hard wired units. Be sure that the branch circuit
or general purpose
outlet is grounded.
VOLTAGE
SUPPLY
Check voltage
supply at outlet.
For satisfactory
results, the voltage
range must always be within the ranges
found on the data information
plate.
Cord - connected
Units
The 250-V field supplied
outlet must match the plug for the standard
208/230-V
units and be within
reach of
the service cord. The standard
cord-connected
265-V units require an accessory
electrical
subbase for
operation.
Refer to Table 2 for proper receptacle
and fuse type.
Power Cord Protection
The power cord for 230/208V
units provide
power cord fire protection.
Unit power automatically
disconnects
when unsafe conditions
are detected.
Power to the unit can be restored
by pressing
the reset button
on plug head.
Upon completion
of unit installation
for 230/208V
models, an operational
check should be performed
using the TEST/RESET
buttons on the plug head.
NOTE: The 265V models do not incorporate
this feature
as they require
use of an electrical
sub-base.
Table
2--RECEPTACLES
AND FUSE TYPES -250,
265 VOLTS
RECEPTACLE
AMPS
15
20
30
15
20
30
RATED VOLTS
250
250
250
265
265
265
TIME-DELAY
TYPE FUSE
15
20 _
30
15
20
30
(or HACR Circuit Breaker)
LEGEND
HACR ---Heating,
Air Conditioning,
Refrigeration
May be used for 15---amp
applications
4