Three-phase AC cabling for Europe (50 Hz)

Connecting the power supply cords

58
Each three-phase HP Disk Array XP1024 DKU has two main disconnect
devices (two main breakers for dual power lines) so that AC power to the
unit can be supplied from separate power distribution panels with two
power-supply cords.
Warning
Trained service personnel should be present whenever the disk array is
being connected to a new power source for the first time. Incorrect power
connections can cause equipment damage and possible injury or death to
personnel.
If you intend to use HP Disk Array XP512 DKUs with your HP XP1024
Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation
Guide for cabling information for these DKUs.
All 50 Hz, European HP Disk Array XP1024 cabinets are shipped with
unterminated power cords. Your electrician must select and install the
correct power plug. Be sure to prepare the following socket receptacles and
power cords between the power distribution board of the building and the
attachment plugs for the unit:
60-amp power cords
Power cords of type H07RN-F or equivalent, with five 10 mm
per cord, are provided with the unit.
Warning
Be sure to connect the power cords to the distribution panel as shown
below. Improper wiring of the neutral conductor may cause damage to your
HP StorageWorks Disk Array XP1024: Site Preparation Guide
2
conductors