The table below lists the basic AC power requirements for a 30-amp,
single-phase XP1024 DKU.
Parameter
Minimum operating voltage (VAC)
Maximum operating voltage (VAC)
Rated line current per power cord
(amps RMS)
Number of power cords
Recommended circuit breakers (amps)
Number of circuit breakers
Dropout carry-through time at
minimum line voltage (ms)
* 60 Hz only.
HP StorageWorks Disk Array XP1024: Site Preparation Guide
Nominal Rated Voltage (VAC)
200 208
220
*
184
191
202
212
220
233
13.5
13.0
12.3
4
4
4
30
30
30
4
4
4
30
30
30
230
240
212
221
244
254
11.7 11.2
4
4
30
30
4
4
30
30