HP StorageWorks XP1024 Manual page 32

Hp storageworks disk array xp1024: site preparation guide (a7906-96013, july 2005)
Hide thumbs Also See for StorageWorks XP1024:
Table of Contents

Advertisement

32
The table below shows the floor load rating for service clearances
(minimum configuration).
Floor load rating
(kg/sq. m)
500
450
400
350
300
Actual clearances for installation should be decided after consulting with
construction specialist responsible for installation building, as they could
vary depending on the size/layout of the system and building conditions.
When various configurations of subsystems are arranged in a row,
clearance values based on the largest subsystem should be used.
From the viewpoint of maintenance operations, it is suggested that
clearance (c) be made as large possible.
HP StorageWorks Disk Array XP1024: Site Preparation Guide
Required clearance (a+b) m
Clearance (c) m
C = 0
C = 0.2
0.6
0.4
0.9
0.7
1.4
1.0
2.0
1.6
3.0
2.5
C = 0.4
C = 0.6
0.2
0
0.4
0.3
0.8
0.6
1.3
1.0
2.1
1.8
C = 1.0
0
0
0.3
0.7
1.3