Manufactured Mobile Home Additional Requirements; Locating Your Ultimate Gas Stove; Louver Installation; Combustion And Ventilation Air - Regency Ultimate U39-NG1 Owners & Installation Manual

Direct vent freestanding gas stove
Table of Contents

Advertisement

INSTALLATION
Minimum ceiling
height is 36"/914mm
from top of unit.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8 ground
lug provided.
3) Appliance must be anchored to the fl oor with
the supplied anchoring methods.
LOCATING YOUR
ULTIMATE GAS STOVE
When selecting a location for your stove, ensure
that the clearances listed above are met as well
as ensuring that there is adequate accessibility
for servicing and proper operation.
10
A) Cross Corner
B) Room Divider
C) Island
D) Flat on Wall
E) Flat on Wall Corner
F) Flush with Wall/ Alcove
For Vent Termination requirements, see
"Exterior Vent termination Locations" section.
LOUVER
INSTALLATION
1)
Attach the top & bottom louvers to the
side stove panel using 2 screws per
side.
COMBUSTION AND
VENTILATION AIR
The combustion air from this appliance is drawn
from outside the building through the outer fl ue.
Extra provision for combustion air inside the
room is not required.
INTRODUCTION
The DV Stove Horizontal Vent Kit and the
Simpson Dura-Vent Direct Vent, venting
systems, in combination with the ULTIMATE
Direct Vent Freestanding Gas Stove, U39-
NG1, and U39-LP1, have been tested and
listed as direct vent heater systems by Warnock
Hersey. If converting a Class-A Metal Chimney
or Masonry Chimney to a Direct Vent system,
see instructions in "Converting a Class-A Metal
Chimney or Masonry Chimey to a Direct Vent
System" section.
These units use the "balanced fl ue" technology
Co-Axial system. The inner liner vents products
of combustion to the outside while the outer
pipe draws outside combustion air into the
combustion chamber thereby eliminating the
need to use heated room air for combustion and
losing warm room air up the chimney.
Note: These flue pipes must not be
connected to any other appliance.
The gas appliance and vent system must be
vented directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each direct vent gas appliance must use it's own
separate vent system. Common vent systems
are prohibited.
Read all instructions carefully before starting the
installation. Failure to follow these instructions
may create a fi re or other safety hazard, and will
void the warranty. Be sure to check the venting
and clearance to combustible requirements.
Consult your local building codes before
beginning installation.
The location of the termination cap must conform
to the requirements in the "Exterior Vent Terminal
Locations" section.
®
Regency
U39 ULTIMATE Direct Vent Freestanding Gas Stove
VENTING
IMPORTANT

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ultimate u39-lp1Ultimate u39

Table of Contents