FPI P36-NG3 Owners & Installation Manual

P36 zero clearance direct vent gas fireplace
Table of Contents

Advertisement

WARNING:
If the information in these instructions are not followed exactly, a fire or
explosion may result causing property damage, personal injury or loss of
life.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
Tested by:
918-062g
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
P36 Zero Clearance
Direct Vent Gas Fireplace
MODELS: P36-NG3 Natural Gas
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
Owners & Installation Manual
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch: do not
use any phone in your building.
Immediately call your gas supplier from a
neighbour's phone. Follow the gas
supplier's instructions.
If you cannot reach your gas supplier, call
the fire department.
P36-LP3 Propane
06/15/05

Advertisement

Table of Contents
loading

Summary of Contents for FPI P36-NG3

  • Page 1 Tested by: Installer: Please complete the details on the back cover and leave this manual with the homeowner. Homeowner: Please keep these instructions for future reference. 918-062g FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4 06/15/05...
  • Page 2 FPI Fireplace. INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE This FPI product has been tested and listed by Warnock Hersey as a Vented Gas Fireplace Heater to the following standards: CAN/CGA-2.17- M91, and ANSI Z21.88b-2003/CSA 2.33b-2003.
  • Page 3: Table Of Contents

    Direct Vent System (Flex) .......... 21 Rigid Pipe Venting Components List ....... 22 Rigid Pipe Venting Systems Horizontal or Vertical Terminations ....23 NOTE: All installation instructions apply to Regency, Hampton & Palace Series unless otherwise specified. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 4 Louvers - Flush ..............49 Double Screen Door ............49 Bay Door ................50 Bay Trim ................50 Bay Louvers ..............50 Finishing Trim ..............51 Full Screen Front .............. 52 Arch Screen Door ............. 54 FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 5: Safety Label

    Massachusetts. For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length. For the State of Massachusetts, the appli- ances individual manual shut-off must be a t-handle type valve. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 6 SAFETY LABEL FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 7: Installation

    A professional service person should IN THE SAME ROOM AS THE APPLI- be called to inspect this appliance annually. ANCE. Make it a practice to have all of your gas appliances checked annually. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 8: Locating Your Gas Fireplace

    A, B, C, D. See ADDITIONAL Diagram 1. REQUIREMENTS 1) Ensure that structural members are not cut or weakened during installation. 2) Ensure proper grounding using the #8 ground lug provided. See page 41. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 9: Clearances

    Barcelona front. HeatWave and Heat Release manual Steel studs and non-combustible material on the facing must be Heat Release Kit for details. adhered to. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 10: Regency Clearances

    REGENCY CLEARANCES Clearances for Bay or Flush Front Clearances for Barcelona Trim HAMPTON CLEARANCES ARCH DOOR CLEARANCES PALACE SERIES CLEARANCES Clearances for The Balmoral & Clearances for The Kensington Front The Westminster Front FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 11: Regency Mantel Clearances

    INSTALLATION FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 12: Hampton Mantel Clearances

    Mantel can be installed anywhere in shaded area or higher using the above scale. Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 13 Mantel can be installed anywhere in shaded area or higher using the above scale. Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 14: Palace Series Mantel Clearances

    Mantel can be installed anywhere in shaded area or higher using the above scale. Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 15: Mantel Leg Clearances

    2" minimum clearance. PALACE SERIES MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram: Kensington Front Width: 42-5/8" Balmoral Front Width: 40-5/8" Westminster Front Width: 40-5/8" Maximum 1-1/2" projection at 2" minimum clearance. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 16: Framing And Finishing

    4) The top of the unit must not be closer than 1-1/2" (38mm) clearance from the vent to 32" (813mm) to the ceiling. combustible material cannot be maintained, e.g. front top header. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 17: Barcelona & Palace Series Framing Note

    When installing the optional Barcelona Front or Palace Series, a non-combustible material 12" (305mm) above the unit and 6" (153mm) on each side must be used. See diagram 1. The Barcelona Front and Palace Series also requires steel stud framing above and on each side of the unit. See diagram 1. Diagram 1 FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 18: Arch Door Series Framing Note

    When installing the optional Arch Door Series, a non-combustible material 12" (305mm) above the unit and 6" (153mm) on each side must be used. See diagram 2. The Arch Door Series also requires steel stud framing above and on each side of the unit. See diagram 2. Diagram 2 FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 19: Unit Assembly Prior To Installation

    Each direct vent gas appliance must use it's own separate vent system. Common vent sys- tems are prohibited. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 20: Exterior Vent Termination Locations

    INSTALLATION EXTERIOR VENT TERMINATION LOCATIONS FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 21: Venting

    Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram on page 20 FPI Direct Vent (Flex) System Termination Kit (Part # 946-515) includes all the parts needed to install the P36 with a maximum run of 4 feet.
  • Page 22: Rigid Pipe Venting Components List

    INSTALLATION RIGID PIPE VENTING COMPONENTS LIST All Simpson Dura-Vent components are available directly from FPI. Description Simpson Dura-Vent Selkirk Amerivent Direct VentGS Direct-Temp Direct Vent 6" Pipe Length, Galvanized 4DT-6 6" Pipe Length, Black 908B 4DT-6B 7" Pipe Length, Galvanized 7"...
  • Page 23: Rigid Pipe Venting Systems Horizontal Or Vertical Terminations

    The FPI AstroCap and FPI Riser Vent terminal is certified for installations using FPI venting systems as well as Simpson Dura-Vent®, Direct Vent GS, American Metal Products, Ameri Vent Direct vent and Selkirk Direct-Temp. FPI , and FPI AstroCap are the proprietary trademarks of FPI Fireplace Products International Ltd.
  • Page 24: Horizontal Terminations

    Firestops are required at each floor level and whenever passing through a wall. NOTE: If you are installing the P36 into a FPI Cabinet Mantel Kit, use the minimum horizontal vent height (centre-line of 40-1/2"). Remember to include the mantel base (3" in height) in your calculations and to maintain the 2" clearance with rigid pipe and flex systems to the underside of the mantel top.
  • Page 25 Please note min. 1 6' Min. 5' Max. 11' Min. 8' Max. foot between 90 7' Min. 6' Max. 12' Min. 9' Max. elbows is required. Lengths do not include elbow indicated FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 26 6' Max. 8' Min. Please note min. 1 foot between 90 elbows is 6' Min. 7' Max. 9' Min. required. 7' Min. 8' Max. 10' Min. Lengths do not include elbow indicated FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 27: Vertical Terminations

    Firestops are required at each floor level and whenever passing through a wall. • Maintain clearances to combustibles. Note: Must use optional rigid pipe adaptor when using rigid pipe vent systems (Part # 510-994). FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 28 Propane and Natural Gas. Maximum two 45 elbows allowed. • Vent must be supported at offsets. • Firestops are required at each floor level and whenever passing through a wall. • Maintain clearances to combustibles. Diagram 1 FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 29: Vertical Terminations - Co-Linear Flex System

    Vertical Termination Cap High Wind Cap 923GK 3" Co-linear Adapter with flashing FPI Cabinet and/or Flat Wall Mantles may be used in these applications ensuring that clearances to com- bustibles are maintained. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 30: Venting Arrangements - Vertical Terminations

    INSTALLATION Venting Arrangements - Vertical Terminations with Co-linear Flex System for both Residential & Manufactured Homes into Masonry Fireplaces The shaded area in the diagrams show the allowable vertical terminations. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 31: Venting - Dura-Vent Horizontal Installations

    Note: Apply sealant "Mill-Pac" to inner down. pipe and high temperature sili- The four wood screws provided should be cone sealant to outer pipe on eve- replaced with appropriate fasteners for Diagram 3 ry twist-lock joint. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 32: Venting - Dura-Vent Vertical Termination

    11/12 to 12/12 1.22 over 12/12 to 14/12 1.52 over 14/12 to 16/12 1.83 over 16/12 to 18/12 2.13 over 18/12 to 20/12 2.29 over 20/12 to 21/12 2.44 Diagram 3 Diagram 7 FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 33: Venting - Installation For Direct Vent System (Flex)

    1" (25mm) clearance is needed at the termination end. We recommend framing 10"(254mm) 10"(254mm) (inside dimensions) hole to give structural rigidity for mounting the termination. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 34: System Data

    Circulation Fan: variable speed 130 CFM. Log Set: Ceramic fibre, 7 per set. 3) Attach manometer to "IN" and/or "OUT" Vent System: Simpson Dura-Vent Direct pressure tap(s) using a 5/16" ID hose. Vent System FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 35: Sit Valve Description

    13) Attach clear label "This unit has been converted to Propane" near or on the serial # decal. Attach white label "This valve has been converted from NG to LPG using SIT conversion Kit Code 0.907.202" onto the valve. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 36: Brick Panels (Optional)

    - do not force into position. 2) Sprinkle the vermiculite around the firebox base. Vermiculite Vermiculite Vermiculite 3) Place the Log 02-49 on the rear log support pins with the flat side to the back. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 37 5) Position Log 02-53 across the cutouts in Logs 02-49 and 02-51 with the notch on the left side of the log fitting into the 2nd grate tab. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 38 02-51 02-54 Log indentation Embers 02-52 Rear Grate 02-54 Photo shows rear grate tab. Log 02-51 was removed to show the positioning of Log 02-52. 02-49 02-52 02-55 02-50 02-54 02-51 FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 39: Standard Flush Door

    Use the hook to pull the spring out until you can put the hook into the slot on the bottom door bracket. Repeat for 2nd spring. See diagram Diagram 1 Diagram 3 To remove the flush door, reverse the above steps. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 40: Remote Control (Optional)

    WALL THERMOSTAT REMOTE CONTROL WALL SWITCH Use the FPI Remote Control Kit approved for this A wall thermostat may be installed if desired, 1) Run the wire through the right or left side unit. Use of other systems may void your connect the wires as per the wiring diagram.
  • Page 41: Wiring Diagram

    Caution: Ensure that the wires do CAUTION: Label all wires not touch any hot surfaces and are prior to disconnection away from sharp edges. when servicing controls. Wiring errors can cause improper and dangerous operation. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 42: Alternative Wiring For Wall Switch

    INSTALLATION ALTERNATE WIRING DIAGRAM FOR WALL SWITCH FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 43: Operating Instructions

    8) The unit should never be turned off, and on again without a minimum of a second Secure left wait. side with 2 screws. Diagram 2 Secure right side with one screw. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 44: Lighting Procedure

    Blower: press the igniter button several times until of the curing process. The glass should FPI gas appliances use high tech blowers to the pilot lights. After approximately one be cleaned or the film will bake on and push heated air farther into the room. It is not minute, release the gas control knob.
  • Page 45: Lighting Plate Instructions

    2) Turn off all electric power to the appliance if service is to be performed. DO NOT REMOVE THIS INSTRUCTION PLATE 908-017b 3) Check for evidences of excessive con- densation, such as water droplets forming FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 46: Gold-Plated Or Brass Louvers

    2) Remove the nuts holding the glass clips in BRASS TRIM place and remove. Your FPI fireplace is supplied with high temper- The 24 carat gold plated or brass finish on the ature, 5 mm Neoceram ceramic glass that will 3) Replace the glass.
  • Page 47: Removing Valve

    8) Disconnect the 2 TP wires and the 2 TH wires from the valve. 9) Remove the 10 Phillips head screws secur- ing the valve tray assembly in place (dia- gram 2) and then lift the entire assembly out (diagram 3). FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 48: Flush & Bay Door Options

    FLUSH & BAY DOOR OPTIONS FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 49: Flush Trim

    2 screws on the left side of the bottom louver. Push down to lock into place. Tighten the screws. Clip locations Clip installed on right side. Burner ON/OFF Screws on control box louver bracket FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 50: Bay Door

    Screws on louver bracket Note: If any maintenance etc. must be done in the firebox, first remove the Bay louvers and door. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 51: Finishing Trim

    6) Hook the bottom finishing trim to the side trims and snap in. 7) Tighten the 2 screws on the left and right hinge bracket to secure. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 52: Full Screen Front

    Frame under the screw heads which were loosened in step 2a. Once the Frame is in place, tighten screws to secure. Bottom Flange Inner Cut-Outs Backside of Full Screen Door Frame Shown FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 53 5) Mount the Burner ON/OFF Control Box to the left side of the Bottom Grill using 2 x #8 Philips Head Screws. Bottom Grill Screen Door Burner ON/OFF Control Box 8) Close screen doors. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 54: Arch Screen Door

    5) Loosen the 3 x #8 Phillips Head Screws located on the inside top of the outer frame of the appliance. Remove bracket Remove both screws 3 x #8 Phillips Diagram 2 FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 55 Repeat step on the other side. Material 1” Facing Material Diagram 2 9) Optional Install Optional 3-Panel Arch Door. (Refer to Install 3-Panel Arch Door Instruction Sheet). 10) Change in Logo Replace existing logo with Regency logo. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 56: Cast Faceplate Option

    CAST FACEPLATE FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 57: Hampton Cast Faceplate

    8) Close bottom louver. 4) Repeat step 3 for the right side faceplate. NOTE: Do not push in side faceplates all the way, allow for room to place the top faceplate. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 58: Hampton Cast Grills

    Black Metallic Grills Only: Mount grill stopper to bottom of firebox securing with one screw. 4) Install new hinge brackets using the same 2 screws removed in step Grill Stopper New hinge bracket. Left side shown. 11) Adjust ball plunger if necessary. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 59 INSTALLATION The Westminster Front The Kensington Front The Balmoral Front FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 60: The Kensington Front

    3) Slide tabs into louver brackets located on the inside top of the firebox. Fan Control Box ON/OFF Switch Wires 6) For optional fan installation, see page 58. 7) For 2-panel & 3-panel door installation, see page 59. Tabs Bracket inside top of firebox. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 61: The Westminster Front

    Westminster Front frame Left Side Shown Valve Fan Control Box ON/OFF Switch Wires 7) For optional fan installation, see page 63. 8) For 2-panel & 3-panel door installation, see page 64-65. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 62: The Balmoral Front

    3) Slide tabs into louver brackets located on the inside top of the firebox. 6) For optional fan installation, see page 63. 7) For 2-panel & 3-panel door installation, see page 64-65. Tabs Bracket inside top of firebox. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 63: Optional Fan Installation

    3) Connect new fan control box wires to the existing fan plug wires (red to red, black to black). Fan Control Box Vertical Hinge Bracket New Fan Control Box FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 64: Panel Door Installation

    The spacer is to be placed over the bottom pin before installing the screen door. 2) Mount 2-panel door frame to flange on sub-frame, ensuring to line up holes. Secure using the 6 screws provided. Spacer FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 65 2) Mount 3-panel door frame to flange on sub-frame, ensuring to line- frame and secure with 2 screws. up holes. Secure using the 4 screws provided. Sub-Frame Secure bottom of sub-frame with screws. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 66: Replacement Parts List

    REPLACEMENT PARTS LIST FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 67: Part List

    946-570 Heat Release Duct Kit (Optional) 108) 910-165 Fan (120 V) 109) 946-000 Flexible Air Release Duct 918-062 Manual 512-969 Conversion Kit - NG to LP *Not available as a replacement part. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 68 910-037 Pilot Orifice LP 79) 512-525 Burner Assy 82) 511-030 Burner Grate Assy 83) 430-101 Rear Log Support Bracket 84) * Deflector 85) 512-930 Log Set *Not available as a replacement part. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 69 Barcelona Assy - Black 161) 948-216 Regency Logo Plate 148) * Barcelona Louver Assy-Black *Not available as a replacement part. 510-932 Flush Glass Trim - Gold (Set) 150) * Flush Glass Trim-Gold FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 70 Bay Front Trim - Brass 120) * Flush Glass Retainer Bracket 780-936 Bay Front Trim - Steel 121) 780-932 Bay Front Screen 122) 948-216 Regency Logo Plate *Not available as a replacement part. FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 71 513-981** Cast Grills (Set) 204) * Top Grill 205) * Bottom Grill *Not available as a replacement part. ** Last digit of part number represents colour: 1=Black Metallic, 5=Enamel Brown, 6=Enamel Black FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 72 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ____________________________________________________________ __________________________________________________________ ____________________________________________________________ _______________________________________________________ _____________________________________________________ __________________________________________________________ _________________________________________________________ _________________________________________________________ ______________________________________________________ ______________________________________________________ _______________________________________________________________ ___________________________________________________________ __________________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ _____________________________________________________________ __________________________________________________________ __________________________________________________________ _____________________________________________________ ________________________________________________________ _________________________________________________________ _________________________________________________________ FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 73 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ____________________________________________________________ __________________________________________________________ ____________________________________________________________ _______________________________________________________ _____________________________________________________ __________________________________________________________ _________________________________________________________ _________________________________________________________ ______________________________________________________ ______________________________________________________ _______________________________________________________________ ___________________________________________________________ __________________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ _____________________________________________________________ __________________________________________________________ __________________________________________________________ _____________________________________________________ ________________________________________________________ _________________________________________________________ _________________________________________________________ FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 74 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ____________________________________________________________ __________________________________________________________ ____________________________________________________________ _______________________________________________________ _____________________________________________________ __________________________________________________________ _________________________________________________________ _________________________________________________________ ______________________________________________________ ______________________________________________________ _______________________________________________________________ ___________________________________________________________ __________________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ _____________________________________________________________ __________________________________________________________ __________________________________________________________ _____________________________________________________ ________________________________________________________ _________________________________________________________ _________________________________________________________ FPI P36-3 Zero Clearance Direct Vent Gas Fireplace...
  • Page 75: Warranty

    This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim. At no time will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufactured.
  • Page 76 Installer: ___________________________________________________________ Phone #: ___________________________________________________________ Date Installed: ______________________________________________________ Serial No.: _________________________________________________________ FPI, Regency, Hampton and The Palace Series are trademarks of FPI Fireplace Products International Ltd. Printed in Canada © Copyright 2005, FPI Fireplace Products International Ltd. All rights reserved.