Installation Procedure - York MLCA-MLHA-07-24 Installation & Owner's Manual

Minisplit high wall air conditioner
Table of Contents

Advertisement

PARTS INSTALLATION
Number Name of part
1
Installation plate
2
Clip anchor
3
Self-tapping screw A ST3.9X25
Liquid side
Connecting
4
pipe
Gas side
assembly
5
Remote controller
6
Self-tapping screw B ST3.9X10
7
Remote controller holder
8
Seal
9
Drain joint
NOTES
Except the above parts provided, the other parts needed
during installation you must purchase.
CAUTIONS
• Ensure that the space around the left and right of the indoor
unit is more than 12cm.
The indoor unit should be installed allowing a minimum clear-
ance of 15cm from the ceiling.
• Use a stud finder to locate studs to prevent unnecessary
damage to the wall.
• A minimum pipe run of 3 metres is required to minimise
vibration & excessive noise.
• The indoor unit should be installed on the wall at a height of
2.3 metres or more from the floor .
• A, B and C directions should be free from obstructions.
NOTES
• This illustration is for explanation purposes only.
• Copper lines must be insulated independently.

INSTALLATION PROCEDURE

INDOOR UNIT
I Fixing
• Place the installation guide pattern on the designated
installation place and mark the hole position.
• Drill a hole and mount installation plate.
• After determining the pipe
hole position. Drill the hole
at a slight downward slant
towards the outdoor side.
Note: When installing
the refrigerant pipes from
others side. A hole must
be place to allow fall
towards the outdoor unit.
8
ENGLISH
J199.pmd
Q'ty
1
8
8
ø 6.35
Parts
ø 9.53 (<12000Btu/h model)
you
ø 12.7 (21000Btu/h model > Cooling
must
capacity f 12000Btu/h model)
purchase
ø 16 (f21000Btu/h model)
1
2
1
1
1
ø 65 mm
Outdoor
Indoor
8
Self-tapping screw B
ST3.9X10
6
5
Remote Controller
holer
Remote Controller
A
B
• Make 6 mm 4-6 holes, in the wall at the four corners of mouting
plate (bracket) then insert appropriate mouting devices.
• Install the mounting plate using 4-6 pieces of mounting screw
securely at four corners and tighten the screw completely.
Do not over tighten the screws and deform the back plate.
MODEL 07-12
150mm or more to ceiling
Indoor unit outline
120mm or more
to wall
Left refrigerant
pipe hole
65
750
( 12000Btu/h model)
MODEL 18
150mm or more to ceiling
Indoor unit outline
120mm or more
to wall
Left refrigerant
pipe hole
65
920
( 12000Btu/h model)
31/03/2005, 9:53 PM
7
4
Loop the
connective
cable.
C
Installation plate
120mm or more
to wall
Right refrigerant
pipe hole
65
Installation plate
120mm or more
to wall
Right refrigerant
pipe hole
65