Service; Coil Replacement; Maintenance Log; Warranty - Greenheck ERS-MD Installation, Operation And Maintenance Manual

Energy recovery laboratory exhaust
Table of Contents

Advertisement

Side or Bottom Intake Opening

Service

Lift
Bracket
Coil Change Out Procedure
Coils can only be pulled out through the side of the
plenum cabinet. Side panels which are nearest to the
Coil
Optional
coil can be removed if the coil needs to be replaced.
External
Piping
Size 020 ERS plenums only have a single coil and do
(by others)
not require coil removal clearances on both sides. If
necessary, both coils can be removed through the
Optional
same side of the plenum housing. This process would
Internal
Piping
require the removal of an additional spacer panel that
(by others)
separates the two coils within the unit.
under
Vektor fans
Cabinet
Size
020
030
040
060
Service Doors
Coil Service
Coil
Clearance

Warranty

Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from
the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option
when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of
one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the
nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Greenheck Catalog Vektor ERS-MD provides additional
information describing the equipment, fan performance,
available accessories, and specification data.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
12
474118 • Model VKERS-MD IOM, Rev. 1, April 2011
Filters
Coil
Service Doors
Internal Pipe
Chase
Bypass
Weatherhood(s)
Vektor bypass
air plenum
optional mounting
Minimum Clearance
locations shown
(inches)
114
74 (each side)
100 (each side)
132 (each side)
Coil Service
Coil
Clearance

Maintenance Log

Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
obtained from AMCA International, Inc. at: www.amca.org.
Copyright 2011 © Greenheck Fan Corp.
S
S
ISOLATION DAMPER
.75" DRAIN