Coil Checklist; Filter Replacement - Greenheck ERS-MD Installation, Operation And Maintenance Manual

Energy recovery laboratory exhaust
Table of Contents

Advertisement

External Pipe
Connection
Internal
Pipe
Chase
6. Pipe sizes for the system must be selected on the
basis of the head [pressure] available from the
circulating pump.
7. Internal coil plumbing. Under each fan there is
a raised, insulated cover panel to be used when
internal pipe connections are desired. Either
remove this panel to run plumbing or punch
appropriately sized holes in the panel to allow
piping to pass without rubbing and space for
piping insulation, sealant and grommets (by
others).
Vent and drain connections are provided on
Greenheck water coils unless otherwise specified.
This allows the coils to be drained. Keep in mind
that when draining the coils, all water may not drain
from the coil. In order to completely drain the coil
to prevent the possibility of freezing during cold
ambient temperatures, air or nitrogen pressure must
be utilized to blow any remaining water from the
coil.
Coil Installation Checklist
Use the following checklist to verify that all necessary
installation procedures have been completed.
1. Coils are installed with airflow in same direction
as indicated on the coil nameplate or casing.
2. Condensate drain pans and piping is installed
with a trap in the condensate line and piping is
insulated and heated if installed in applications
that are below freezing.
3. Clean filters are installed upstream.
CW4R,6R,8R COIL RIGHT OUTLET
462708
VINYL
PAINT
PART NO.
MAT'L
PURCHASED
COILCONNECTION
LABELCW-RIGHT
The original drawing. Dan Jore asked me to edit 8/10/2010.
Remove the border and the two cap drawings.
External Pipe
Connection
Internal
Pipe
Chase
NOTE

Filter Replacement

Filters are located only in the coil plenum section.
1
DESCRIPTION
QTY
Access is needed from both sides of the plenum to
OLUND_T
IAN7664
462682
VINYL
CW4R,6R,8R COIL LEFT OUTLET
MSCF-15,20,25
11/20/2002
PAINT
PART NO.
MAT'L
30,45,50,65,85
change all the filters. Unit may have either 2 inch
1/1
MERV 8 filters or 4 inch MERV 11 filters depending on
PURCHASED
COILCONNECTION
the application requirements. Use equivalent MERV
LABELSCW-LEFT
rating filters when replacing.
The original drawing. Dan Jore asked me to edit 8/10/2010.
Remove the border and the two cap drawings.
Change the filters regularly. Pressure drop readings
can be used to determine when a filter should be
replaced. Prefilters should be replaced at filter
manufacturers recommended pressure drop change
out or as required by system design.
All filter sections have access provided by a door.
Filters used in Greenheck ERS plenums can be
changed in most cases by sliding them out and
replacing. In some cases, filters are secured to frames
using a clip.
Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust