CHAPTER 1 Installation Information
Noise [dB]
Acoustic power level [B]
Allowable vibration
[m/s
Allowable dust concentration [mg/m
Power requirements Input voltage and number of phases
Frequency and fluctuation range
Maximum power
consumption/
apparent power
Power factor (*7)
Rush current [A] (Inrush time) (*8)
Leakage current [mA] (*9)
*1 The dimensions do not include protrusions.
*2 The values are for the device with all options installed.
However, the values do not include the weight of mounted rack-mount rails (7 kg) and cables.
*3 If the intake air temperature is high (but within the normal temperature range), the fan enters high-speed mode
even when operation is normal.
*4 Condensation is not permitted.
*5 The temperature requirements depend on the altitude at the installation site.
- Installation at 0 to 500 m (0 to 1640 ft.) above sea level: 5 to 35°C (41 to 95.0°F)
- Installation at 500 to 1000 m (1640 to 3281 ft.) above sea level: 5 to 34°C (41 to 93.2°F)
- Installation at 1000 to 1500 m (3281 to 4921 ft.) above sea level: 5 to 33°C (41 to 91.4°F)
- Installation at 1500 to 3000 m (4921 to 9843 ft.) above sea level: 5 to 30°C (41 to 86.0°F)
The altitude specifications for the installation site include an allowable margin of error of ±100 m.
*6 "Non-operating" refers to the condition where a device has been disconnected from the power supply and stored.
*7 This is the value during operation.
*8 This value is for a single input cable.
*9 This value is for a single device.
Item
Operating (including standby state)
2
(gal)]
Non-operating (*6)
Operating
Standby
3
]
Input voltage: 200 V
Input voltage: 100 V
Input voltage: 200 V
Input voltage: 100 V
10
Description
(Included in main
unit specifications)
(Included in main
unit specifications)
4.0 (400) (synthetic
seismic waves)
10.0
(1000) (synthetic
seismic waves)
0.15
200 to 240
VAC ±10%
100 to 120
VAC ±10%
50/60 Hz +2/-4%
450 W / 475 VA
460 W / 485 VA
10 W / 40 VA
10 W / 35 VA
0.95 or more
25 or less
3.5 or less
C122-H004-07EN