PRIMEQUEST 1000 Series Hardware Installation Manual
CHAPTER 1 Installation Information
Weight [kg (lb)] (*2)
Air conditioning
Maximum heat output [kJ/h (BTU/h)]
requirements
Exhaust air
flow [m
(ft
3
/min)] (*3)
Temperature
and humidity
requirements
(*4)
Noise [dB] (*7) (*8)
Acoustic power level [B] (*8)
Allowable
vibration [m/
s
2
(gal)]
Allowable dust concentration [mg/m
Power
Input voltage and number of phases
requirements
Frequency and fluctuation range
Maximum
power
consumption/
apparent
power
Power factor (*10)
Rush current [A] (Inrush time) (*11)
Leakage current [mA] (*12)
*1 The dimensions do not include protrusions.
*2 The values are for the device with all options installed.
However, the values do not include the weight of mounted rack-mount rails (7 kg) and cables.
You can use the following formula to calculate the weight of the device based on its configuration:
Equipment weight = 86 + (11 x A) + (8 x B) + (2 x C)
Item
FAN at low speed (Low)
3
/min
FAN at normal speed (Normal)
FAN at high speed (High)
Operating
Non-operating (*6) Temperature [°C (°F)]
Operating (including standby state)
Non-operating (*9)
Operating
Standby
Temperature [°C (°F)]
Humidity [%RH]
Maximum wet-bulb
temperature [°C (°F)]
Humidity [%RH]
Maximum wet-bulb
temperature [°C (°F)]
3
]
Input voltage: 200 V
Input voltage: 200 V
8
Description
150 (330)
14,400 (13,649)
14 (494)
21 (742)
24 (848)
(*5)
20 to 80
29 (84.2)
0 to 50 (32 to 122)
8 to 80
29 (84.2)
61
7.8
4.0 (400) (synthetic seismic
waves)
10.0 (1000) (synthetic
seismic waves)
0.15
200 to 240 VAC ±10%
Single phase
50/60 Hz +2/-4%
4.00 kW / 4.21 kVA
95 W / 126 VA
0.95 or more
20 or less
3.5 or less
C122-H004-07EN