Gas Supply - Empire Heating Systems SR-10T-3 Installation Instructions And Owner's Manual

Unvented room heater
Table of Contents

Advertisement

The gas line can be routed either through the floor or wall. The gas
line opening should be made at this time. Location of the opening
will be determined by the position of floor joists and the valve and
union used for servicing.

Gas Supply

Check all local codes for requirements, especially for the size and
type of gas supply line required.
Recommended Gas Pipe Diameter
Pipe Length
Schedule 40 Pipe
Inside Diameter
Nat.
0-10 feet
1/2"
0-3 meters
12.7mm
10-40 feet
1/2"
4-12 meters
12.7mm
40-100 feet
1/2"
13-30 meters
12.7mm
100-150 feet
3/4"
31-46 meters
19mm
Note: Never use plastic pipe. Check to confirm whether your local
codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
Dimensions Apply to SR-10T, SR-18T and SR-30T
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the
unit. Where none exists, or where its size or location is not ad-
equate, contact your local authorized installer for installation or
relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. It is required
16941-5-0907
GAS SUPPLY
Tubing, Type L
Outside Diameter
L.P.
Nat.
L.P.
3/8"
1/2"
3/8"
9.5mm
12.7mm
9.5mm
1/2"
5/8"
1/2"
12.7mm
15.9mm
12.7mm
1/2"
3/4"
1/2"
12.7mm
19mm
12.7mm
1/2"
7/8"
3/4"
12.7mm
22.2mm
19mm
Figure 1
by the National Fuel Gas Code that a drip line be installed near
the gas inlet. This should consist of a vertical length of pipe tee
connected into the gas line that is capped on the bottom in which
condensation and foreign particles may collect.
Method of Installing a Tee Fitting Sediment Trap (Figure 2)
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tub-
ing and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction.The state of Massachusetts requires that a flex-
ible appliance connector cannot exceed three feet in length.
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T.
plugged tapping, accessible for test gauge connection, must be
placed immediately upstream of the gas supply connection to
the appliance.
2. The appliance and its appliance main gas valve must be discon-
nected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig (3.5
kPa).
3. The appliance must be isolated from the gas supply piping sys-
tem by closing its equipment shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal
to or less than 1/2 psig (3.5 kPa).
Attention! If one of the above procedures results in pressures in
excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve,
it will result in a hazardous condition.
Checking Manifold Pressure
Natural gas will have a manifold pressure of approximately 6.0"
w.c. (1.49kPa) at the pressure regulator outlet with the inlet pressure
to the pressure regulator from a minimum of 7.0" w.c. (1.743kPa)
for the purpose of input adjustment to a maximum of 10.5" w.c.
(2.615kPa). Propane/LP gas will have a manifold pressure ap-
proximately 10.0" w.c. (2.49kPa) at the pressure regulator outlet
with the inlet pressure to the pressure regulator from a minimum
of 11.0" w.c. (2.739kPa) for the purpose of input adjustment to a
maximum of 13.0" w.c. (3.237kPa).
A test gage connection is located downstream of the gas appliance
pressure regulator for measuring gas pressure. The connection is
a 1/8 inch (3mm) N.P.T. plugged tapping.