Table 18
Electrical data—Quiet-Line models (95°F/35°C) 60Hz
Nominal
Capacity
Model #
Tons
Characteristic
27
2
37
3
42
3.5
67
5
*
FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Model # 14, 20 and 96 are not available in Quiet-Line versions.
Table 19
Electrical data—Standard sound and ambient models (95°F/35°C) 50Hz
Nominal
Capacity
Model #
Tons
Characteristic
13
1
19
1.5
26
2
36
3
41
3.5
66
5
95
8
*
FLA = Full Load Amps
Table 20
Electrical data—High ambient models (105°F/41°C) 50Hz
Nominal
Capacity
Model #
Tons
Characteristic
13
1
19
1.5
26
2
36
3
41
3.5
66
5
95
8
*
FLA = Full Load Amps
Input Voltage-Phase
* Electrical
208/230-1
FLA
13.0
WSA
16.0
OPD
25
FLA
18.8
WSA
23.3
OPD
40
FLA
—
WSA
—
OPD
—
FLA
—
WSA
—
OPD
—
Input Voltage-Phase
* Electrical
220-1
FLA
9.9
FLA
10.9
FLA
12.7
FLA
18.4
FLA
—
FLA
—
FLA
—
Input Voltage-Phase
* Electrical
220-1
FLA
—
FLA
—
FLA
14.8
FLA
20.5
FLA
—
FLA
—
FLA
—
208/230-3
460-3
575-3
—
—
—
—
—
—
—
—
—
12.3
6.4
5.2
15.2
7.8
6.4
25
15
15
14.8
6.9
5.9
18.3
8.5
7.3
30
15
15
21.1
10.9
8.8
25.9
13.4
10.8
45
20
15
200/230-3
380/415-3
—
—
—
—
—
4.9
—
7.0
15.3
8.5
24.1
13.2
—
20.3
200/230-3
380/415-3
—
—
—
—
—
6.0
—
13.1
19.8
9.6
24.2
13.2
—
—
23
Installation