110 Appendix B: NT5C10CO shelf
UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001
OPEN
Note 1:
At this point, one rectifier may indicate an RFA. An RFA
may be indicated when a rectifier delivers less than 0.1 A
(see Note 2). Turning the FLT potentiometer slightly
clockwise will return it to normal operation, with no
RFA.
Note 2:
Sends an alarm at no load condition, only for the
following releases or under.
NT5C06BB,BB-1,BB-3,BC
NT5C06CA,CA-1,CA-3,CA-5,CC Rel.10
NT5C06CB,CB-1,CB-3,CD
NT5CO6CE-61(-46)
OPEN
6
5
4
3
2
1
CLOSED
6
5
4
3
2
1
Rel.12
CLOSED
Rel.10
Rel.12