Canadian Applications

Appendix F
This section illustrates the connection of the 411UD Digital Alarm Communicator/Transmitter (DACT) to an FACP
for Canadian Applications. The following conditions must be adhered to in order to comply with Canadian require-
ments.
Only one FACP can be connected to the 411UD DACT.
1.
Phone lines must exit the building in separate directions.
2.
The 411UD DACT relay must be enabled [refer to "Output Relay Enable (87)" on page 36] and must be
3.
programmed to activate on DACT trouble [refer to "Output Relay Function Selections (88)" on page 37].
The Auxiliary Trouble Input wiring from the 411UD DACT must be in conduit and in the same room as the
4.
FACP and DACT.
Channel 4 (2.2K ELR)
jumper -VDC to relay terminal
+24 VDC nonresettable power
-24 VDC nonresettable power
64
Canadian Applications
N.O relay contact (DACT Trouble) from 411
FACP Supervision Relay
FACP Trouble Relay
FACP
411UD
J4 (under cover) jumper not installed
FACP Alarm Relay
2.2K ELRs P/N 27070
Document #50759 Rev. E 12/09/2008 P/N 50759:E
411UD
Auxiliary Trouble Input
(nonsupervised, power-limited)