Downloading To The Communicator; Uploading From The Communicator - Fire-Lite 411UD Manual

Digital alarm communicator/transmitter
Hide thumbs Also See for FIRE-LITE 411UD:
Table of Contents

Advertisement

Downloading to the Communicator

Central Station Acknowledge
There is an option whereby the communicator will report to one or both Central Stations that a request for upload-
ing or downloading has been received prior to processing the call. This is called the 'callback' option. If the Cen-
tral Station(s) does not acknowledge receipt of this request, uploading or downloading is prohibited. If
acknowledged by the Central Station(s), another message is transmitted informing the Central Station(s) that:
• downloading was successful
• uploading was successful
• uploading/downloading was not successful
Data Protection/Integrity
Programming data is completely verified for accuracy prior to reprogramming of the 411UD EEPROM. Incom-
plete or corrupted data packets are ignored or retried.
5.2
Downloading to the Communicator
Before initiating the download procedure, make certain that the communicator is in the standby state; red Line Seize
and green Modem LEDs are off.
Once an incoming call is accepted/answered by the communicator, the 411UD will:
Establish basic modem connection
1.
Verify secret code
2.
Verify callback vs. no callback request from the Service Terminal. If callback is requested, perform steps 4
3.
through 10; if no callback is requested, perform steps 9 and 10 only.
Identify the Service Terminal location
4.
Hang-up/disconnect call
5.
Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If
6.
this message is accepted, the communicator will proceed to the next step
Return call to the Service Terminal
7.
Verify secret code
8.
Begin downloading
9.
Upon completion of download, call the Central Station(s) back and report a successful download or failed
10.
upload/download status (if programmed to do so).
5.3

Uploading From the Communicator

Items that may be uploaded from the communicator to a Service Terminal are:
• All or portions of programmed data plus the real time clock
• Troubleshoot system voltages in real-time or as a 'snapshot'
• Current system status in real-time continuous or as a 'snapshot'
Uploading is possible at any time provided the following conditions are true:
The communicator may be in any mode of operation. Uploading is not possible if the communicator is
active or while testing the phone lines while in Troubleshoot Mode.
There cannot be any active communications ongoing with a Central Station receiver.
All active events must be successfully 'kissed-off' by the Central Station(s). The communicator must be
in a standby state with no new information waiting to be transmitted to a Central Station.
48
411UD
Document #50759 Rev. E 12/09/2008 P/N 50759:E

Hide quick links:

Advertisement

Table of Contents
loading