Program Mode
Input Channel 1 Delay Timer (69 - 71)
The Delay Timer is used to delay activation of the digital communicator when the Input Channel is activated.
Input Channel 1 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a
delay of from 0 to 179 seconds. Inputs programmed for fire alarm, host control panel trouble and fire supervi-
sory, must not be delayed. A delay, therefore, cannot be selected for inputs programmed for these fire applica-
tions.
Input Channel 2 Delay Timer (72 - 74)
The Delay Timer is used to delay activation of the digital communicator when the Input Channel is activated.
Input Channel 2 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a
delay of from 0 to 179 seconds. Inputs programmed for fire alarm, host control panel trouble and fire supervi-
sory, must not be delayed. A delay, therefore, cannot be selected for inputs programmed for these fire applica-
tions.
Input Channel 3 Delay Timer (75 - 77)
The Delay Timer is used to delay activation of the digital communicator when the Input Channel is activated.
Input Channel 3 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a
delay of from 0 to 179 seconds. Inputs programmed for fire alarm, host control panel trouble and fire supervi-
sory, must not be delayed. A delay, therefore, cannot be selected for inputs programmed for these fire applica-
tions.
Input Channel 4 Delay Timer (78 - 80)
The Delay Timer is used to delay activation of the digital communicator when the Input Channel is activated.
Input Channel 4 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a
delay of from 0 to 179 seconds. Inputs programmed for fire alarm, host control panel trouble and fire supervi-
sory, must not be delayed. A delay, therefore, cannot be selected for inputs programmed for these fire applica-
tions.
Touchtone/Rotary Select for Primary Phone (81)
A '0' programmed in this address by the factory, triggers Touchtone dialing over the primary phone line. Select '1'
for rotary dialing.
Make/Break Ratio for Primary Phone (82)
This address is used only if a '1' has been programmed for address 81. The Make/Break ratio is factory set to '0'
which is 67/33 ratio, but may be changed to '1' which is 62/38 ratio.
Touchtone/Rotary Select for Secondary Phone (83)
A '0' programmed in this address by the factory, triggers Touchtone dialing over the secondary phone line. Select
'1' for rotary dialing.
Make/Break Ratio for Secondary Phone (84)
This address is used only if a '1' has been programmed for address 83. The Make/Break ratio is factory set to '0'
which is 67/33 ratio, but may be changed to '1' which is 62/38 ratio.
Reserved for Future Use (85)
Reserved for Future Use (86)
Output Relay Enable (87)
The factory default setting for the Output Relay is '1' for enabled. Enter '0' to disable the relay.
1. This timer does not delay LED or Output Relay activation and is not used for channels programmed as AC Loss circuits.