Optional Programmer

2.6
Optional Programmer
The optional Fire-Watch 411 Series DACT Programmer (Model PRO-411) is used to:
switch between the digital communicator's five Modes of operation
set the digital communicator's 24 hour internal clock in Real-Time Clock Mode
program the 411UD digital communicator in Program Mode
test the telephone lines interconnect in Troubleshoot Mode
return all digital communicator programming to the factory default settings in Default Mode
To use the PRO-411 Programmer:
Remove all power from the 411UD
1.
Remove the two screws holding the 411UD cover in place and remove the cover
2.
Connect the Programmer cable to connector J2 located in the upper right corner of the 411UD. Note that the
3.
key on the connector must align with the slot in the J2 connector
Reapply power to the 411UD
4.
Operate the Programmer by pressing the MODE key. Enter the appropriate four digit code and then press the
5.
[ENTER/STORE] key.
Note that it is not possible to switch from Normal Mode to any other mode if any of the four Channels is programmed
for fire alarm or fire supervisory, and is active, that is, in alarm (shorted).