Program Mode
Enter the remaining numbers in their respective addresses as shown below:
4
8
4
7
Entry
Address
30 31 32 33 34 35 36 37 38 39 40
Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the numeric digits as
dialed numbers and the hexadecimal digits representing the following functions:
• A = * on a Touch-Tone phone keypad
• B = # on a Touch-Tone phone keypad
• C = look for secondary dial tone for up to two seconds (then dial anyway)
• D = three second pause
• E = five second pause
• F = end of phone number (Note: F must remain in all unused phone number addresses)
Secondary Central Station Number Communication Format (50)
One location is needed to select the Communication Format to the secondary phone number. Address 50 is used
for this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0'
through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use
The Format selected in address 50 will cause the digital communicator to automatically program addresses 202 - 265
with the factory default settings. Any of the Event Code settings may be altered. Consult your Central Station prior
to altering the event code settings. An entry of all zeros for any event code will cause the communicator to NOT
transmit the report. Transmission of reports to either or both Central Station phone numbers may be disabled.
Refer to "Central Station Communications" on page 40 for information on Format reporting.
Upon accessing the first address which is 202 (Refer to Table 3-5, "4+2 Standard and 4+2 Express Formats - Second-
ary," on page 32), the following may be displayed on the Programmer's 7-Segment Display, if the corresponding For-
mat was selected in address 50.
The first three locations on the left of the Programmer's display represent the memory address 202. The last location
1 (farthest right) represents the contents of memory address 202 which is the first digit of the event code.
1
6
1
F
F
F
F
2021