10-3. O,OI terminal adjustment procedure

If you need fine adjustment with out F31 IN EX%S, IN EX%E function(DOP/DRW), or A group A13,A14
function (on standard panel), please refer to following procedure.
set C91 "01"
; Debug on
set C94 "F947"
; O terminal adjustment constant
set C95 "xx"
; adjust this data
power off and wait Power lamp off and power on and check the freq. setting.
(set C91 "01"
; Debug on)
set C94 "F948"
; OI terminal adjustment constant
set C95 "xx"
; adjust this data
power off and wait Power lamp off and power on and check the freq. setting.
set C91 "00"
; Debug off
If the data was added, the freq. setting will be increased. (concept is as same as J100,J300)