Installation of Optional Module

2.7
Installation of Optional Module
CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring.
2.7.1 4XTMF Transmitter Module
Push the disconnect switch to the down position to prevent accidental activation of the municipal box during
testing of the control panel. The Disconnect LED will remain illuminated while the municipal box is
disconnected. The System Trouble LED will indicate disconnected and/or open circuit conditions on the
municipal box. During trouble conditions, it is possible to obtain the circuit condition on the alarm reverse
polarity output. If this operation is desired, cut the TBL jumper on the 4XTMF module.
4XTMF Module Connections
FIGURE 2-10:
TROUBLE
SIGNAL
INITIAT
OUTPUT
ZONE 1
-
-
+
NC
C
NO
+
Cut R14 for 4XTMF module
placement supervision
24
INITIAT
ZONE 2
-
+
TB2
CUT IF 4X
OPTION
BOARD IS
PRESENT
R14
TBL Jumper
Install 4XTMF Module by
plugging into connector
J6
and
J7
on CMP-2401B/02B main
board
J3
BATTERY
SW1
SW2
SW3
SW4
CUT TO
DISABLE
J4
EARTH
FAULT
R72
J1
Document #50907
Rev.A1
12/03/02
4XTMF Module
Polarities are shown for
module activation
1 (+)
Remote Alarm (power-limited)*
2 (-)
3 (+)
Remote Trouble (power-limited)*
4 (-)
5
no connection
6 (+)
Municipal Box (nonpower-limited)*
7 (-)
* Wiring from these terminals can
exit the protected premises.
Disconnect Switch
Disconnect LED
P/N 50907:A1