Operating Power

2.3
Operating Power
!
WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power
before servicing. The panel and associated equipment may be damaged by removing and/or inserting modules,
interconnecting cables or wiring while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The AC input circuit is limited by fuse F2 (2 amp,
3AG Slow Blow). The primary power source for the FACP is 120 VAC, 60 Hz, 0.5 amps. Run a pair of wires (with
ground conductor) from the protected premises main breaker box to TB3 of the main circuit board. As per the
National and Canadian Electric Code, use 14 AWG (2.00 mm
lation. No other equipment may be connected to this circuit. In addition, this circuit must be provided with overcur-
rent protection and may not contain any power disconnect devices. A separate Earth Ground connection must be
made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire [mini-
mum 14 AWG (2.00 mm
tion since this does not provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J3 on the main circuit board using the
plug-in connector and cable provided. The battery charger is current-limited and capable of recharging sealed lead
acid type batteries. The charger shuts off when the system is in alarm. See Battery Calculations for calculation of the
correct battery rating.
!
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics.
If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate
medical attention.
Operating Power Connections
FIGURE 2-4:
Grounding Stud
AC
20
2
)] to the grounding stud on the backbox. Do not use conduit for the Earth Ground connec-
AC
BUZ
+24V
GND
TBL
ALARM
REG
NC
C
NO
NC
RES
TB1
J5
Earth
F2
TB3
Hot
Neutral
Document #50907
2
, 1.6 mm O.D.) or heavier gauge wire with 600V insu-
TROUBLE
SIGNAL
INITIAT
INITIAT
-
OUTPUT
ZONE 1
-
ZONE 2
-
C
NO
+
+
+
TB2
SW1
SW2
SW3
SW4
CUT IF 4X
OPTION
BOARD IS
PRESENT
R14
CUT TO
DISABLE
J4
EARTH
FAULT
J3
J1
BATTERY
Rev.A1
12/03/02
R72
P/N 50907:A1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cmp-2402b

Table of Contents