Figure 5-5
Field Wiring of the Optional Audio Visual Power Supplies (AVPS-24F/
AVPS-24FE)
Auxiliary Bell
Power Harness
Black wire
Blue wire
For the first or only AVPS-24F in a Sensiscan
2000, connect the AVPS-24F Trouble Cable
(71033) to P5 on the MPS-24AF or P4 on the
MPS-24BF for supervision. Otherwise con-
nect as illustrated below.
Earth Ground In
Connect to chassis or Earth
Ground Terminal on the
main power supply.
Secondary Power
(24 VDC Batteries)
Connect to:
MPS-24AF: TB2-1 (+) and TB2-2 (-)
MPS-24BF: TB3-1 (+) and TB3-2 (-)
For multiple
Audio Visual
Power Supplies
To P5 on MPS-24AF;
or to P4 on the MPS-
24BF.
36
Unfiltered, unregulated, power-limited (3.0 amps max). Use Auxiliary
Bell Power Harness to provide power to notification circuit modules
(connect to J5 on IC-4F or ICE-4F).
P3
Trouble
LED
+
-
First AVPS-24F
S2000 15017 Rev H 10/08/96 P/N 15017:H
24 VDC Bell Power
+
-
1
2
TB2
TB1
Earth Ground Out
Connect to TB1 Terminal 1
on next AVPS-24F.
Hot
Neutral
Primary Power
120 VAC for AVPS-24F
220/240 VAC for AVPS-24FE
Connect to:
MPS-24AF: TB1-5 (Neutral) and TB1-7 (Hot)
MPS-24BF: TB1-3 (Neutral) and TB1-4 (Hot).
Last AVPS-24F