Programming Options
CHAPTER 3
This chapter describes the programming options available by cutting resistors on the FACP main circuit board.
Options should be selected (resistors cut if necessary) prior to applying power to the control panel.
3.1

Earth Ground Fault Detection

The FACP is factory configured to automatically detect ground fault conditions. A ground fault occurs when a low
resistance is detected between an FACP circuit and earth ground. This condition will cause the System Trouble LED
and Ground Fault LED to turn on and the piezo sounder to pulse.
The Ground Fault Detection circuit can be disabled by cutting resistor R72 on the main circuit board. Refer to the
local codes and consult the local Authority Having Jurisdiction before disabling the Ground Fault Detection circuit.
Ground Fault Detection Circuit
FIGURE 3-1:
TB3
3.2

Optional 4XTMF Transmitter Module Placement Supervision

The 4XTMF module can be used to connect the FACP to a City Box or Reverse Polarity Remote Station. To super-
vise placement and operation of the module, cut resistor R14. Refer to the local codes and consult the local Authority
Having Jurisdiction before installing the 4XTMF Transmitter Module.
4XTMF Module Placement Supervision
FIGURE 3-2:
J5
26
Programming Options
Document #50907
CUT TO
DISABLE
J4
EARTH
FAULT
J3
J1
BATTERY
SW4
CUT IF 4X
OPTION
BOARD IS
PRESENT
R14
Rev.A1
12/03/02
P/N 50907:A1
R72
R72
Cut to Disable Ground
Fault Detection
R14
Cut to Supervise Placement
of 4XTMF Module when
installed