Chapter 1: Product Description; Product Features - Fire-Lite CMP-2401B Instruction Manual

Fire alarm control panel
Hide thumbs Also See for CMP-2401B:
Table of Contents

Advertisement

Product Description
CHAPTER 1
The CMP-2401B is a one zone FACP (Fire Alarm Control Panel) and the CMP-2402B is a two zone FACP. This
manual will use the term FACP to refer to both the CMP-2401B and CMP-2402B where features are identical. These
control panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institu-
tional buildings. The FACPs use conventional input devices such as two-wire smoke detectors, four-wire smoke
detectors, pull stations, waterflow devices and other normally-open contact devices. Outputs include one NAC (Noti-
fication Appliance Circuit) and 24 volt resettable power. The FACP also supervises all wiring, AC voltage and bat-
tery level.
Activation of a compatible smoke detector or any normally open fire alarm initiating device will activate audible and
visual signaling devices, illuminate an indicating LED and sound the piezo at the FACP, activate the FACP alarm
relay and operate an optional module used to notify a remote station or initiate a supplementary control function.
1.1

Product Features

• Style B (Class B) Initiating Device Circuit (IDC)
CMP-2401B - one IDC
CMP-2402B - two IDCs
• One NFPA Style Y (Class B) Notification Appliance Circuit (NAC)
• Form-C Alarm Relay
• Form-C Trouble Relay
• Control switches
Reset
Trouble Silence
Signal Silence - Zone One
Signal Silence - Zone Two (CMP-2402B only)
• LED Indicators
AC Power
Zone Alarm and Trouble
Bell Trouble
Option Module Trouble
System Trouble
Zone Silence
Ground Fault
Battery Trouble
• Piezo Sounder for alarm and trouble signal
• Dress Panel coverplate
• 24 volt operation
• Small backbox size
• Low AC voltage sense
• Silence Inhibit Notification Appliance Circuit
• Automatic Battery Float Charger
• Battery Deep Discharge Protection
• Optional Remote Trouble Buzzer
Product Description
Document #50907
Rev. A1
12/03/02