Central Station Communications
The digital communicator is capable of reporting detailed messages depending upon the Format in use. Table 4-1
shows the data reporting structure for each of the pulsed formats as well as the Ademco Express Formats. Ademco
Express Formats allow a typical data message to be transmitted to the Central Station in under 5 seconds. Pulsed for-
mats typically require 15 to 20 seconds in comparison. Table 4-2 defines each letter code used in Table 4-1 . See
"Ademco Contact ID Format Event Code Description" on page 42 for a description of the data reporting structure for
Ademco Contact ID Format.

Format Selection Addresses ( 20 and 50) Programming

TABLE 4-1:
Report
Fire Alarm
Fire Alarm Restore
Channel/Input Trouble
(Channel/Input Open)
Channel/Input Trouble
Restore
System Trouble
System Trouble Restore
AC Loss
AC Loss Restore
Fire Supervisory Condition
Fire Supervisory Condition
Restore
Test Report
411 Communicator
Format #
Format #
0, 2, 4, 6, 8
3, 5, 7, 9
3+1/4+1/Standard
3+1/4+1/Expanded
4+1 Express
SSS(S) FA
SSS(S) FA
FAFAFA(FA) 2
SSS(S) RFA
SSS(S) RFA
RFARFARFA (RFA) 2
SSS(S) TZ
SSS(S) TZ
TZTZTZ(TZ) Z
SSS(S) RTZ
SSS(S) RTZ
RTZRTZRTZ(RTZ) Z
SSS(S) TS
SSS(S) TS
TSTSTS(TS) Y
SSS(S) RTS
SSS(S) RTS
RTSRTSRTS(RTS) Y
SSS(S) P
SSS(S) P
PPP(P) Z
SSS(S) RP
SSS(S) RP
RPRPRP(RP) Z
SSS(S) V
SSS(S) V
VVV(V) Z
SSS(S) RV
SSS(S) RV
RVRVR(RV) Z
SSS(S) X
SSS(S) X
Document #50921
Rev. E
Format #
1, A, C
4+2/Standard 4+2
Express
SSSS FAFA2
SSSS RFARFA2
SSSS TZTZ2
SSSS RTZRTZ2
SSSS TSTS2
SSSS RTSRTS2
SSSS PP2
SSSS RPRP2
SSSS VV2
SSSS RVRV2
SSSS XX2
12/09/2008
P/N 50921:E
Format #
B, D
4+2/Expanded
SSSS FAZ
SSSS RFAZ
SSSS TZZ
SSSS RTZZ
SSSS TSY
SSSS RTSY
SSSS PP2
SSSS RPRP2
SSSS VZ
SSSS RVZ
SSSS XX2
39