Program Mode
Secondary Central Station Number Communication Format (50)
One location is needed to select the Communication Format to the secondary phone number. Address 50 is used
for this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0'
through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use
The Format selected in address 50 will cause the digital communicator to automatically program addresses 202 - 265
with the factory default settings. Any of the Event Code settings may be altered. Consult your Central Station prior
to altering the event code settings. An entry of all zeros for any event code will cause the communicator to NOT
transmit the report. Transmission of reports to either or both Central Station phone numbers may be disabled.
Refer to "Central Station Communications" on page 38 for information on Format reporting.
Upon accessing the first address which is 202 (Refer to Table 3-5, "4+2 Standard and 4+2 Express Formats - Second-
ary," on page 32), the following may be displayed on the Programmer's 7-Segment Display, if the corresponding For-
mat was selected in address 50.
The first three locations on the left of the Programmer's display represent the memory address 202. The last location
1 (farthest right) represents the contents of memory address 202 which is the first digit of the event code.
The following Tables list the data which is automatically programmed for each Format that can be selected in address
50. The addresses shown in each Table contain the event code Setting data which is automatically programmed by
the 411. To change the value, key in the new digits and then press the [ENTER/STORE] key to save the new value.
Use the Up and Down Arrow keys to increment to the next address or decrement to the previous address.
Ademco Contact ID Format Secondary Central Station Event Codes
If E is entered for address 50, the following data is automatically programmed for the Secondary Central Station
phone number event codes. Enter '000' for the Setting to disable the report to the Central Station.

Ademco Contact ID Format - Secondary

TABLE 3-4:
Address
Description
202 - 204
Secondary # Input Channel 1 Active Event Code
205 - 207
Secondary # Input Channel 2 Active Event Code
208 - 210
Secondary # Input Channel 3 Active Event Code
211 - 213
not used
411 Communicator
2021
(address)(data)
Document #50921
Rev. E
12/09/2008
Setting
110
373
200
P/N 50921:E
Channel/
Input #
001
002
003
31