Programming Sheets; Digital Communicator Options Program Sheets - Fire-Lite 411 Manual

Digital alarm communicator/transmitter
Hide thumbs Also See for 411:
Table of Contents

Advertisement

Programming Sheets

Appendix A
A.1 Digital Communicator Options Program Sheets
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
00
01
02
Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number.
Primary Central Station Communication Format: Valid entries are 0 to 9 and A to F.
20
21
22
23
25
26
27
Primary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
29
30
31
32
Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.
Secondary Central Station Communication Format: Valid entries are 0 to 9 and A to F.
50
51
52
53
55
56
57
Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
59
AC Loss Reporting Delay. Enter '0' for no delay; '1' for 1 hours; '2' for 2 hours; '3' for 6 hours; '4' for 7 hours;
60
'5' for 8 hours; '6' for 9 hours; '7' for 10 hours; '8' for 11 hours; '9' for 12 hours; 'A' for 13 hours; 'B' for 14 hours; 'C' for
15 hours; 'D' for 16 hours; 'E' for 17 hours; 'F' for 18 hours.
Backup Reporting. Enter '0' to report to Secondary phone number as backup only; '1' to report to both Primary
61
and Secondary phone number for all reports/messages; '2' reports go to first available receiver.
Reserved for Future Use.
62
Reserved for Future Use.
63
Communicator Enable/Disable. Enter '0' to disable communication to Central Station; '1' to enable. Default
64
entry of '0' causes the 411 to annunciate a DACT trouble immediately on power-up.
Input Channel 1 Function Selection. Enter '0' for fire alarm; '1' for host control panel trouble; '2' for fire super-
65
visory; '4' for AC loss.
Input Channel 2 Function Selection. Enter '0' for fire alarm; '1' for host control panel trouble; '2' for fire super-
66
visory; '4' for AC loss.
Input Channel 3 Function Selection. Enter '0' for fire alarm; '1' for host control panel trouble; '2' for fire super-
67
visory; '4' for AC loss.
Future use.
68
69
70
71
delay. Does not delay Input Channels programmed for fire functions.
72
73
74
delay. Does not delay Input Channels programmed for fire functions.
44
Programming Sheets
03
04
05
06
07
Primary Central Station Account Code: Valid entries are 0 to 9 and A to F.
24
Primary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
28
33
34
35
36
37
Secondary Central Station Account Code: Valid entries are 0 to 9 and A to F.
54
Secondary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
58
Input Channel 1 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no
Input Channel 2 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no
411 Communicator
08
09
10
11
12
38
39
40
41
42
Document #50921
Rev. E
12/09/2008
13
14
15
16
17
43
44
45
46
47
P/N 50921:E
18
19
48
49