Downloading Initiated at a Service Terminal

3.3 Downloading Initiated at a Service Terminal

3.4 Uploading Initiated at a Service Terminal

DACT-UD PN 51899:B1 1/25/05
Before initiating the Download procedure, make certain that the control panel is in the
standby state with the red Line Seize LED, green Modem and Kissoff LEDs off.
Once an incoming call is accepted/answered by the control panel, the panel will:
1. Establish basic modem connection
2. Verify secret code
3. Verify callback vs. no callback request from the Service Terminal. If callback is
requested then perform steps 4 through 10. If no callback is requested then
perform steps 9 and 10 only
4. Identify the Service Terminal location
5. Hang-up/disconnect call
6. Call the Central Station(s) and transmit a request for upload/download message
(if programmed to do so). If this message is accepted, the control panel will
proceed to the next step
7. Return call to Service Terminal
8. Verify secret code
9. Begin downloading
10. Upon completion of download, call Central Station(s) back and report a
successful download or failed upload/download status (if programmed to do so)
Items that may be uploaded from the control panel to a Service Terminal are:
All or portions of programmed data plus the real time clock, time and date
Entire Walktest data file in real-time continuous or as a 'snapshot'
Troubleshoot system voltages in real-time continuous or as a 'snapshot'
Entire event History file
Current system status in real-time continuous or a a 'snapshot'
Uploading is possible at any time provided the following conditions are true:
The control panel may be in any mode of operation. Uploading is not possible
if the communicator is active or while testing the phone lines while in
troubleshoot mode
There cannot be any active communications ongoing with a Central Station
receiver
All active events must be successfully 'Kissed-off' by the Central Station(s).
The communicator must be in a standby state with no new information waiting
to be transmitted to a Central Station
Programming for DACT-UD
39