Programming for DACT-UD

3.2 Remote Site Upload/Download

36
The control panel may be programmed or interrogated off-site via the public switched
telephone network. Any personal computer with Windows 95, a 1200 baud Hayes
compatible modem and Fire•Lite Upload/Download software P/N PK-CD may serve as
a Service Terminal. The Upload/Download software allows the following:
Download of the entire program
Download of an individual program item
Upload of the entire program
Upload of an individual program item
Upload of the entire program plus history file, walktest data, current status,
system voltages and time & date
Real-time upload, either continuous or 'snapshot' (one time) of current status
or system voltages
Execution of control panel functions such as Trouble Silence, Manual
Evacuate, Manual Evacuate Restore, Zone/NAC Disable, Zone/NAC Enable
and Set Time & Date
WARNING: Changes to program entries occur as a result of the downloading process.
After successful downloading, make certain to perform the following steps:
1. Print out all programmed data via print mode or manually view programmed
entries and compare to intended program data
2. Test all affected panel operations
3. Immediately correct any problems found
3.2.1 Downloading Program: General
Any time that the control panel is downloaded, whether initiated at the jobsite or
remotely, a secret code (Factory Default 0000) is verified between the control panel and
the Service Terminal. Changing the Secret Code may only be accomplished at the
Service Terminal and subsequently loaded into the control panel. Future upload or
download requests cause verification of the secret code by the control panel before
processing of data is allowed. If the secret code is not verified, the control panel will
terminate the request immediately.
While the control panel is communicating with the Service Terminal, the DACT-UD's
green Modem LED and one of the red Line Seize LEDs will remain on steady. At the
conclusion of a successful download transaction, the green Kissoff LED will come on
steady for one second. Upon termination of communication, the green Modem LED
will turn off and the red Line Seize LED will turn off.
In order to download the panel (whether initiated at the jobsite or remotely) the
following must be true:
The control panel may be in any mode of operation, including Disable, Enable
and Drill. Downloading is not possible if the communicator is active during
Central Station communications or while testing the phone lines while in
Troubleshoot mode
There cannot be any active communications ongoing with a Central Station
receiver
All active events must be successfully 'Kissed-off' by the Central Station(s)
The communicator must be in a standby state with no new information waiting
to be transmitted to a Central Station