Fan Pulley Alignment; Pulley And Drive Adjustment; Condensate Drains; Return-Air Filters - Bryant 524J Installation, Start-Up And Service Instructions Manual

Packaged air-handling units 60 hz with puron (r-410a) refrigerant sizes 07, 08, 12, 14, 16
Table of Contents

Advertisement

Fig. 22 — Fan Rotation
Fan Pulley Alignment —
1. Loosen setscrews on pulleys.
2. Align pulleys visually and tighten setscrews on fan pulley
to lock it in place.
3. Use the methods shown in Fig. 23 to check proper pulley
alignment.
4. If pulleys are not in correct alignment, loosen the motor
holddown bolts and slide the motor axially until the
pulleys are aligned.
5. Tighten motor holddown bolts.
Pulley and Drive Adjustment —
fan speed, refer to the fan motor and drive data in Tables
8A-11D and adjust fan motor pulley as follows:
1. Remove belt from fan motor pulley after loosening motor
from motor base.
2. Loosen setscrew in moveable flange of pulley. Screw
moveable flange toward fixed flange to increase the fan
speed and away from fixed flange to reduce speed.
Before tightening setscrew, make certain that setscrew is
over nearest flat surface of pulley hub (Fig. 23).
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Increasing fan speed produces a greater load on motor. Do
not exceed rated capacity of motor.
Condensate Drains —
dirt and foreign matter.
Align as follows:
To obtain desired
Keep condensate drains free of
Fig. 23 — Fan Pulley Adjustments
Return-Air Filters —
for filter accessibility and removal. Replace with clean filters of
the sizes listed in Tables 1A-1D.
Coil Removal —
required. Disconnect coil connections and remove fastening
screws. Remove coil through end or side sections of unit.
Cleaning Cooling Coil —
Remove any heavy dirt that may have accumulated on under-
side of coil. Coil can be cleaned more easily with a stiff brush,
vacuum cleaner, or compressed air when coil is dry. If coil is
wet or if water is to be used for cleaning, guard against splash-
ing water on electrical components or damaging surrounding
area. Clean coil baffles as applicable and check for tight fit to
be sure air does not bypass coil.
Cleaning Insulation —
mobilized antimicrobial agent that helps prevent the growth of
bacteria and fungi. Clean the inner surface of the insulation
according to the separate maintenance instructions shipped
with the unit.
22
Refer to Replacing Filters section
Remove unit panels and corner posts as
Remove return-air filters.
The insulation contains an im-

Advertisement

Table of Contents
loading

Table of Contents