AC Receptacle Selection
The generator
has two separate
main power producing
circuits.
These two circuits
supply
equal power to different
receptacles
shown
when the voltage
selector
switch
is in the 120/24OV po-
sition.
When two or more receptacles
are used; prevent overloading
by
dividing
the load between the two power circuits.
The chart below shows the rated load in amperes
that can be
connected
to each receptacle to balance the generator.
The total rated ampere draw is 25.OA.
Main power circuit
Receptacles powered
Power distribution
by each main circuit
Main Circuit I
2,3and4
2+3+4=12.5A
rated.
Main Circuit II
1 and 5
1 -I- 5=12.5A rated.
*The table shows the specifications
when the 120/24OV locking
plug receptacle is used for 120V.
Example:
Receptacle 2 has a IOA load connected
to it. Receptacle 3 has a IO
A load connected
to it. Both receptacles
are powered
by main
power circuit II. The equation
tells us that the total power draw on
circuit
II is 25A. This is a substantial
overload
of this circuit.
To
eliminate
the excess
power
draw on circuit
II, the load from
receptacle
3 should
be switched
to receptacle
1. Now circuit
I is
powering
the IOA load (less than 12.5A) and circuit II is powering
the IOA load (less than 12.5A).
1 ii;
;g
(GFCI,
6 120/24OV 20A
@ 120/24OV 20A
(LOCKING PLUG)