Cooling Requirements - HP StorageWorks 2/32 - SAN Switch Installation Manual

Version 4.2.x
Hide thumbs Also See for StorageWorks 2/32 - SAN Switch:
Table of Contents

Advertisement

Installing the SAN Switch 2/32

Cooling Requirements

Cooling air is drawn into the switch chassis by the fans mounted on the rear of the
chassis. The air is expelled through vents in the front (port side) of the chassis,
next to the HP logo. HP recommends installing the switch so that air intake and
exhaust for all components in the rack is flowing in the same front-to-back
direction.
Note:
reside in the front of the cabinet and the ports (cables) reside in the rear of the cabinet.
Follow these guidelines to ensure proper air flow and prevent component
overheating:
24
HP highly recommends mounting the switch in a cabinet or rack so that the fans
To ensure adequate cooling, install the switch with the non-port side, which
contains the air intake vents, facing the cool-air aisle.
Verify that a minimum of 47 cubic feet/minute (79.8 cubic meters/hour) of air
flow is available to the air intake vents on the non-port side of the switch.
Verify that the ambient air temperature does not exceed 40° Celsius (104°
Fahrenheit) while the switch is operating.
Caution:
Do not block air vents. The switch uses ambient air for cooling.
SAN Switch 2/32 Version 4.2.x Installation Guide