Table A-1
Example Power Consumption (Theoretical Maximum) and Air
Conditioning Requirement Summary
Component
Chassis
Cell Board (PA8700)
PCI Card (Maximum 25W)
Power Supply (BPS)
DVD
Disk Drive
Core I/O
PCI Power Supply
Table A-2
Power Consumption (Theoretical Maximum) and Air Conditioning
Requirement Summary
Component
Chassis
Cell Board (PA8700)
PCI Card (Maximum 25W)
Power Supply (BPS)
DVD
Disk Drive
Core I/O
PCI Power Supply
Appendix A
Multiply
Quantity
Quantity
By:
1
426
2
746
16
25
2
125
1
20
4
25
2
70
2
47
Total
Multiply
Quantity
Quantity
By:
1
426
746
25
125
20
25
70
47
Total
System Requirements Summary
Power Consumption and Air Conditioning
Power
Dissipated
Required (tons)
(kilowatts)
(kilowatts/3.517
426.00 (.426)
0.121
1492.00 (1.492)
0.424
400.00 (.400)
0.114
250.00 (.250)
0.071
20.00 (.020)
0.006
100.00 (.100)
0.028
140.00 (.140)
0.040
94.00 (.094)
0.027
2922.00 (2.922)
.831
Power
Conditioning
Dissipated
Required (tons)
(kilowatts)
(kilowatts/3.517
=tons)
426.00 (.426)
0.121
Air
Conditioning
=tons)
Air
43