Computer Room Safety

Computer Room Safety
Inside the computer room, fire protection and adequate lighting (for equipment servicing) are important
safety considerations. Federal and local safety codes govern computer installations.

Fire Protection

The national Fire Protection Association's Standard for the Protection of Electronic Computer Data
Processing Equipment, NFPA 75, contains information on safety monitoring equipment for computer rooms.
Most computer room installations are equipped with the following fire protection devices:
Smoke detectors
Fire and temperature alarms
Fire extinguishing system
Additional safety devices are:
Circuit breakers
An emergency power cutoff switch
Devices specific to the geographic location i.e., earthquake protection

Lighting Requirements for Equipment Servicing

Adequate lighting and utility outlets in a computer room reduce the possibility of accidents during equipment
servicing. Safer servicing is also more efficient and, therefore, less costly.
For example, it is difficult to see cable connection points on the hardware if there is not enough light.
Adequate lighting reduces the chances of connector damage when cables are installed or removed.
The minimum recommended illumination level is 70 foot-candles (756 lumens per square meter) when the
light level is measured at 30 inches (76.2 cm) above the floor.