DRAFT INDUCER KIT WITH CONTROL KIT
(NOTE: DI PAK MVFG units are designed for the Flame Guard units built
by American Water Heater. All other manufacturers use DI PAK MV)
This draft inducer kit is designed for installation onto vent systems serving
30 millivolt standing pilot gas fired water heaters with gas valves having a
manifold pressure tap port (1/8 FPT)
NOTE: DI-1 Model must be used on 4" diameter vent pipe.
I
TEMS INCLUDED IN KIT
CAUTION: Draft inducers are designed to increase draft in venting applications where inadequate natural draft exists.
This device is NOT designed for sidewall venting applications. The vent to which the inducer is to be mounted is to be
installed in accordance with NFPA 54, NFPA 31, or other local codes.
This device MUST be installed by a qualified installer in accordance with the manufacturers installation instructions.
Appliances should have a maximum measure flue gas temperature of 750°F at the desired location of the draft inducer.
"Qualified Installer" shall mean an individual who has been properly trained or a licensed installer. The installer MUST
write or imprint his name, phone number, and date of installation on the tag provided with this device. The tag MUST be
attached to the draft inducer. Recording burner and draft inducer operation information (draft level, efficiency, etc) is
recommended as a guide for future service.
Model: DI PAK MV & DI PAK MVFG
1) DI-1,2 or 3 Draft Inducer with pre-attached power cable
1) Fan control gas pressure switch with built in post purge option and pre-wired power cord
1) 1/8" NPT x 3 inch pipe nipple
1) 1/8" NPT pipe tee
1) TCA-1 Thermocouple Adapter (DI PAK MV)
1) TCA-2 Left Handed Thermocouple Adapter (DI PAK MVFG)
1) 6 ft. length of 12-2 wire
1) 12 inch jumper wire
1) Flexible conduit connector
2) GSK-3 Spillage Switch
DO NOT DESTROY
THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT

Advertisement

loading

Summary of Contents for Field Controls 46477000

  • Page 1 DRAFT INDUCER KIT WITH CONTROL KIT Model: DI PAK MV & DI PAK MVFG (NOTE: DI PAK MVFG units are designed for the Flame Guard units built by American Water Heater. All other manufacturers use DI PAK MV) This draft inducer kit is designed for installation onto vent systems serving 30 millivolt standing pilot gas fired water heaters with gas valves having a manifold pressure tap port (1/8 FPT) NOTE: DI-1 Model must be used on 4”...
  • Page 2 INSTALL THE DI-SERIES DRAFT INDUCER ON THE FLUE PIPE (Figure 1) 1. Refer to the included DI instruction manual for this procedure. Set the draft adjustment plate on the draft inducer to maximum setting before installing NOTE: The draft inducer proving switch (DIP-1) and DI-CK Control Kit adapter kit are not required with the DI PAK MV and MVFG kits.
  • Page 3 IV. WIRING CAUTION: Disconnect electrical power when wiring power venter Wire the draft inducer motor and controls in accordance with the National Electrical Code, manufacturer's recommendations and/or applicable local codes. Units must be grounded. Check ground circuit to make certain that the unit has been properly grounded.
  • Page 4 GSK-3 Spillage Switch 46086400 TCA-1 46082700 TCA-2 (Flameguard Only) 46429900 DI-1 46073000 DI-2 46075300 DI-3 46090700 INSTALLATION INFORMATION DI- PAK MV(FG) MODEL NO.:____________________________________________________________ INSTALLER'S NAME:_____________________________________________________ INSTALLER'S COMPANY: _________________________________________________ INSTALLER'S PHONE NO.: ________________________________________________ DATE OF INSTALLATION:_________________________________________________ P/N 46477000 11/04 Page 4...

This manual is also suitable for:

Di pak mvDi pak mvfg