Equipment Data

EQUIPMENT DATA for brine-to-water heat pumps for heating purposes
TYPE AND COMMERCIAL DESCRIPTION
1
MODEL
2
2.1
Enclosure type acc. to EN 60 529
2.2
Installation site
PERFORMANCE DATA
3
3.1
Operating temperature limits:
Heating water supply
Brine (heat source)
Antifreeze agent
Minimum brine concentration (-13°C freezing temperature)
3.2
Heating water temperature difference at B0 / W35
3.3
Heating capacity / coeff.of perform.
3.4
Sound power level
3.5
Sound pressure level at a distance of 1 m
3.6
Heating water flow rate at internal pressure difference
3.7
Brine flow rate at internal pressure difference (heat source)
3.8
Refrigerant; total charge weight
DIMENSIONS; CONNECTIONS AND WEIGHT
4
4.1
Equipment dimensions without connections 4)
4.2
Equipment connections for heating system
4.3
Equipment connections for heat source
4.4
Weight of transport unit(s) incl. packaging
ELECTRICAL CONNECTION
5
5.1
Nominal voltage; fusing
5.2
Nominal power consumption
5.3
Starting current with soft starter
5.4
Nominal current B0 W35 / cosϕ
COMPLIES WITH EUROPEAN SAFETY REGULATIONS
6
OTHER DESIGN CHARACTERISTICS
7
7.1
Water inside equipment protected against freezing
7.2
Performance settings
7.3
Controller internal / external
These data characterize the size and performance capability of the system. For economic and energetic reasons, additional factors such as balance point and control need to be
1)
taken into consideration. Abbreviations have the following meaning, e.g. B10 / W55: heat source temperature 10 °C and heating water supply temperature 55 °C.
2)
The heating circulating pump and the controller of the heat pump must be on standby at all times.
3)
See EC Declaration of Conformity
4)
Please keep in mind that additional space is required for pipe connections, operation and maintenance.
5)
2-compressor operation
6)
1-compressor operation
Subject to technical modifications
°C
°C
K
at B-5 / W55
1)
kW / ---
kW / ---
at B0 / W50
1)
kW / ---
kW / ---
at B0 / W35
1)
kW / ---
kW / ---
dB(A)
dB(A)
m³/h / Pa
m³/h / Pa
Type / kg
H x W x L mm
inches
inches
kg
V / A
1)
B0 W35
kW
A
5)
A / ---
2)
APPENDIX: 12.2 EQUIPMENT DATA
..50ZSN
..75ZSN
IP 21
indoors
indoors
max. 60
max. 60
-5 to +25
-5 to +25
monoethylene glycol
monoethylene glycol
25%
25%
8,9
9,9
5)
37,5 / 2,4
59,8 / 2,3
6)
15,0 / 2,1
30,1 / 2,2
5)
43,8 / 3,0
69,8 / 2,9
6)
18,5 / 2,5
33,3 / 2,8
5)
46,7 / 4,5
75,2 / 4,4
6)
23,0 / 4,4
37,6 / 4,3
65
69
50
54
4,5 / 2000
6,5 / 2500
12,8 / 15700
20,5 / 17800
R404A / 8,6
R404A / 12,6
1890 x 1350 x 750
1890 x 1350 x 750
G 1 1/2'' i/ext.
G 2'' i/ext.
G 2 1/2'' i/ext.
G 2 1/2'' i/ext.
486
571
400 / 50
400 / 63
10,45
16,95
56
105
18,9 / 0,8
30,58 / 0,8
3)
3)
yes
yes
2
2
internal
internal
Issued: 02.11.2005
15
..100ZSN
IP 21
IP 21
indoors
max. 60
-5 to +25
monoethylene glycol
25%
9,7
76,2 / 2,5
33,6 / 2,4
87,9 / 3,1
39,1 / 2,8
96,3 / 4,6
48,4 / 4,6
71
55
8,5 / 3600
24,0 / 18600
R404A / 20,5
1890 x 1350 x 750
G 2'' i/ext.
G 3'' i/ext.
652
400 / 80
20,93
120
37,8 / 0,8
3)
yes
2
internal