INSTALLATION INSTRUCTIONS
MA5IN / MA8IN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AUBURN 8 and is the answer not in the manual?

Questions and answers

Summary of Contents for Masport AUBURN 8

  • Page 1 INSTALLATION INSTRUCTIONS MA5IN / MA8IN...
  • Page 2 Glen Dimplex Australia proudly supports the activities of Landcare Australia through its membership of the AHHA. MA5IN/MA8IN (AUBURN 5 INBUILT / 8 INBUILT) VERSION 1.0...
  • Page 3: Table Of Contents

    Technical Drawings ......13 6.1. Masport Auburn 5 Inbuilt (MA5IN) ..13 6.2.
  • Page 4: Important Information

    If you suspect your child has swallowed or inserted a All Masport wood heaters have been tested to ensure button battery immediately call the 24-hour Poisons that they will meet the appropriate safety Standard...
  • Page 5: Masonry Installation

    If a combustible mantelpiece is present, a Mantelpiece Shield must be installed (refer to section “2.3. Mantelpiece Shield”). CLEARANCES MASONRY INSTALLATION AUBURN 5 AUBURN 8 A (Width between mantelpiece columns) 822mm...
  • Page 6: Floor Protector (Hearth)

    The floor protector may be laid directly on the combustible floor. • For more details and variations on floor protectors refer to AS/NZS 2918 Clause 2.2, 3.3.1, & 3.3.2. CLEARANCES FLOOR PROTECTOR AUBURN 5 AUBURN 8 VENTILATED VENTILATED Hearth Construction (or equivalent)
  • Page 7: Mantelpiece Shield

    2.2.1. VENTILATED HEARTH OPTION The Mantelpiece Shield can extend to fit a mantelpiece with a depth greater than 140mm, following these steps: A ventilated hearth can be used instead of a brick hearth. The hearth must be constructed from non-combustible If required, trim width of shield to suit width of material such as cement sheet with tiles (with thermal mantelpiece.
  • Page 8: Zero Clearance Installation

    6 X Wafer Head Timber Screws #10 x 45mm enclosure with minimum clearances to combustible materials from the appliance determined in accordance with AS/NZS 2918. VENTED OUTER Auburn 5 shown in diagram. CASING ENCLOSURE These are minimum clearances and may be installed with CHANNELS greater clearances if desired.
  • Page 9 SIDE WALL ENSURE GAP FOR VENTILATION BEHIND HEATER STEEL CHANNEL TOP VIEW ENCLOSURE CHANNEL ASSEMBLY VENTED OUTER CASING ZERO CLEARANCE BASE ON 740mm x 480mm CEMENT SHEET FRONT VIEW...
  • Page 10: Enclosure Ventilation

    3.3. ENCLOSURE VENTILATION of cement sheet with a minimum thickness of 5mm, measuring 740mm wide x 480mm deep. Any wider, and Enclosure ventilation allows cooler air into the base of the it will restrict the ventilation from the lower vents past the enclosure and hot air to escape into the room.
  • Page 11: Power Supply For Fan

    Ventilated hearth option” on page 5. CLEARANCES FLOOR PROTECTOR - HEATER 245MM OR MORE ABOVE FLOOR (FROM BOTTOM OF MAIN FASCIA) AUBURN 5 AUBURN 8 Hearth Construction (or equivalent) HEAT-RESISTANT MATERIAL HEAT-RESISTANT MATERIAL...
  • Page 12: Extended Fascia Options

    (supplied separately) to fill any gaps between the main fascia and enclosure. Four extended fascia options are available for each model (Auburn 5 or Auburn 8). Fascia 4 Sided 50mm (50mm visible edges) Fascia 4 Sided 100mm (100mm visible edges) With main fascia removed from the heater, the extended fascia can hook onto its inside edge.
  • Page 13: Installing The Baffle

    - see above diagram. Note that the profile of baffle rail. Once clear of the right rail, push the the Front Baffle Retainer varies betwen Auburn 5 and baffle to the right side of the heater in order to Auburn 8 - Auburn 5 front retainer pictured above.
  • Page 14: Installing The Fire Bricks

    INSTALLING THE FIRE BRICKS Place the bricks into the firebox as shown in the diagrams below for the Auburn 5 and Auburn 8. Once bricks are in, fit the retainer over the top to hold them in place. Auburn 5: •...
  • Page 15: Technical Drawings

    TECHNICAL DRAWINGS 6.1. MASPORT AUBURN 5 INBUILT (MA5IN) 643.5 643.5 321.8 321.8 534.3 534.3 449.3 449.3 LEFT FRONT LEFT FRONT 6.2. MASPORT AUBURN 8 INBUILT (MA8IN) 743.5 743.5 371.8 371.8 553.3 553.3 468.3 468.3 LEFT FRONT LEFT FRONT...
  • Page 20 Glen Dimplex Australia Pty Ltd 8 Lakeview Drive, Scoresby Victoria 3179 Australia T: 1300 554 155 General and Sales Enquiries: flame.care@glendimplex.com.au Technical Service: flame.support@glendimplex.com.au www.glendimplex.com.au...