Technical Specifications - STEINEL PRESENCE CONTROL PRO Manual

Presence control pro
Table of Contents

Advertisement

Available languages

Available languages

Electrical installation/Automatic mode
In selecting the wiring leads, it is
VDE 0100 520 permits the use of a
important to meet the wiring regu-
multiple-conductor cable contain-
lations laid down in VDE 0100 (see
ing both the mains-voltage wires
Safety warnings on page 20). The
as well as the control lines (e.g.
following applies to wiring pres-
NYM 5 x 1.52) for the wiring be-
ence detectors: Section 6 of
tween sensor and electronic bal-
COM 1
COM 2
L
L
L
N
N
N
P
P S N
COM1
L L'
B1
B2
COM 1 AP
last. The mains supply lead must
be no greater than 10 mm in dia-
meter. The clamping range of
the mains terminal is designed
for a maximum of 2 x 1.5 mm
2
1 x 2.5 mm
.
DIM
L
N
P
P S N
COM2
L L' B1 B2
max. 1 A
B1
B2
- 22 -

Technical Specifications

Dimensions (H x W x D):
Power supply:
Capacity, switching output 1:
(COM 1/COM 2)
2
or
Electronic ballast:
(COM 1/COM 1 AP/COM 2/DIM)
Capacity, switching output 2:
(COM 2 only)
Square detection zones:
Light-level setting:
Switching output 1:
Time setting
Switching output 2:
Time setting
DIM:
Time setting
Control output:
Installation height:
(mounted to ceiling)
Installation site:
Sensors:
Enclosure:
Protection class:
Temperature range:
120 x 120 x 76 mm
230 – 240 V, 50 Hz / 60 Hz
230 V relay
resistive load of 2000 W max. (cos φ = 1)
1000 VA max. (cos φ = 0.5)
Max. 'ON' current 800 A/200 μs
30 x (1 x 18 W), 25 x (2 x 18 W)
25 x (1 x 36 W), 15 x (2 x 36 W)
20 x (1 x 58 W), 10 x (2 x 58 W)
Pay attention to specific 'ON' currents of electronic ballasts!
A relay or contactor must be provided on line side for higher
switching capacities.
Presence
max. of 230 W/230 V
1A max., (cos φ = 1) for HVAC (heating/ventilation/air conditioning)
IR Quattro
IR Quattro HD
Presence: max. of 4 x 4 m (16 sq.m.)
max. of 8 x 8 m (64 sq.m.)
Radially: max. of 5 x 5 m (25 sq.m.)
max. of 8 x 8 m (64 sq.m.)
Tangentially: max. of 7 x 7 m (49 sq.m.)
max. of 20 x 20 m (400 sq.m.):
10 – 1000 lux, ∞ / daylight /
DIM 100 – 1000 lux control threshold
30 sec. – 30 min., pulse mode (approx. 2 sec.),
IQ mode (automatic adjustment to the usage profile)
COM2 only, for HVAC
0 sec. – 10 min. switch-'ON' delay
1 min. – 2 hrs. stay-'ON' time
Automatic room surveillance
30 sec. – 30 min.,
IQ mode (automatic adjustment to the usage profile)
1 – 10 V / max. of 50 electronic ballasts, max. of 100 mA
2.5 m – 8 m (IR Quattro)
2.5 m – 10 m (IR Quattro HD)
indoors
13 detection levels, 1760 switching zones (IR Quattro)
13 detection levels, 4800 switching zones (IR Quattro HD)
IP 20
II
0° C to +40° C
- 23 -

Hide quick links:

Advertisement

Table of Contents