Wall mounted universal controller

Advertisement

TCI-W11, TCI-W22 Series Wall Mounted Universal Controller
Features
Universal PID and/or binary control for any analog
input/output signal and range.
Multiple auxiliary functions: heat-cool auto changeover,
automatic enable, setpoint compensation.
Differential, averaging, min and max functions
Cascading of control loops (-W22 type).
Alarm monitoring of low and high limits on all inputs.
Programmable reaction in case of alarm.
Feedback function for inputs and set points.
Functions for dehumidifying, set point shift, cascade control.
Password protected programmable user and control
parameters.
Blue backlight.
TCI-W22 also includes
Power Cap protected real-time clock with 48hr power backup.
Clock with up to 8 switching events.
7-day programmable schedules, with options including
change of setpoints and direct position of manual outputs.
Applications
Fan coil units
Heat exchangers
Zoning
General
TCI-W11: 1 independent control loop, 1 internal temperature sensor, 1 universal input (analog/binary/temp),
2 binary/PWM outputs, 1 analog output
TCI-W22: 2 independent control loops, 8 time schedules, 1 internal temperature sensor, 2 universal inputs,
2 binary/PWM outputs, 1 analog output
Internal temperature sensor standard. Add replaceable humidity element as required: AES3-HT-A2 (2%), AES3-
HT-A3 (3%), or AES3-HT-A5 (5%)
Flexible application configuration is made with a parameter-setting routine using the standard operation terminal.
Product Name
- W
T
C
I
2
Types and Ordering
Product
Product No.
Name
TCI-W11
40-10 0257
TCI-W11-H
40-10 0258
TCI-W22
40-10 0261
TCI-W22-H
40-10 0262
AES3-HT-A2
40-50 0102
AES3-HT-A3
40-50 0103
AES3-HT-A5
40-50 0104
Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy:SDB-Tn10-20 (duct), SRA-Tn10
(room), SDB-Tn10-20 + AMI-S10 as immersion sensor.
Actuators: Choose modulating actuators with an input signal type of 0-10 V DC or 4-20 mA (Min. and max. signal
limitations may be set with parameters.3-point actuators with constant running time are recommended.
Binary auxiliary devices (e.g. pumps, fans, on/off valves, humidifiers, etc): Do not directly connect devices that exceed
specified limits in technical specifications – observe startup current on inductive loads.
Doc: 70-00-0158C, V2.0-20220523
Subject to alteration
VAV
Air handlers
Fan, Pump control
-
2
U
Housing
In/Outputs:
Control loops:
Mounting:
Series:
Temperature
Humidity
Loop
Sensor
Sensor
(internal)
(internal)
1
1
2
© Vector Controls GmbH, Switzerland
TCI-W11, TCI-W22 Universal Controller
Humidifiers
Dehumidifiers
Ventilation
Blank = square housing
See table below
1 = 1 control loop, 2 = 2 control loops
W = Wall mounted
TCI
Universal
Binary
Input
Output
0
1
1
2
0
2
1
1
1
1
Radiant heating
Radiant cooling
Pressurization
Time
Analog
Schedules
Output
0
rH Sensor 3% acc.
1
Time schedules
8
rH Sensor 3% acc.
rH Sensor 2% acc.
rH Sensor 3% acc.
rH Sensor 5% acc.
O
VERVIEW
TCI-W11
TCI-W22
Option
Standard
Page 1-22