Phoenix Contact EMM 3- 24DC/500AC-16-IFS User Manual

Phoenix Contact EMM 3- 24DC/500AC-16-IFS User Manual

Motor management
Table of Contents

Advertisement

RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx
User manual
UM EN CONTACTRON
Motor Management

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EMM 3- 24DC/500AC-16-IFS and is the answer not in the manual?

Questions and answers

Summary of Contents for Phoenix Contact EMM 3- 24DC/500AC-16-IFS

  • Page 1 User manual UM EN CONTACTRON Motor Management RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 2 Designation Order No. EMM 3- 24DC/500AC-IFS 2297497 EMM 3-230AC/500AC-IFS 2297507 EMM 3- 24DC/500AC-16-IFS 2297523 EMM 3-230AC/500AC-16-IFS 2297536 EM-PB-GATEWAY-IFS 2297620 IFS-USB-PROG-ADAPTER 2811271 IFS-CONFSTICK-L 2901103 IFS-CONFSTICK 2986122 UT 4-MTD-R/CVC 690/SET 2901667 CONTACTRON-DTM-IFS 2297727 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 3 How to contact us Internet Up-to-date information on Phoenix Contact products and our Terms and Conditions can be found on the Internet at: www.phoenixcontact.com Make sure you always use the latest documentation.
  • Page 4 The receipt of technical documentation (in particular user documentation) does not consti- tute any further duty on the part of Phoenix Contact to furnish information on modifications to products and/or technical documentation. You are responsible to verify the suitability and intended use of the products in your specific application, in particular with regard to observ- ing the applicable standards and regulations.
  • Page 5: Table Of Contents

    Setting the PROFIBUS address ............4-6 4.2.7 Setting the INTERFACE system address ..........4-8 PROFIBUS telegrams..................4-10 4.3.1 Structure of the parameterization telegram ........4-10 4.3.2 Structure of the diagnostic telegram ..........4-11 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 6 7.2.2 Connection to the PC ................7-5 7.2.3 Connection to the device ..............7-5 7.2.4 Technical data ..................7-6 Software setup ....................7-7 7.3.1 Installation ...................7-7 7.3.2 Uninstallation ..................7-8 7.3.3 Configuration ..................7-9 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 7 Example 7 - Reversing starter with connection to PROFIBUS ......8-16 8.7.1 Hardware configuration ..............8-16 8.7.2 Software configuration ..............8-17 Example 8 - 690 V reversing starter with voltage transducer ......8-18 8.8.1 Hardware configuration ..............8-18 8.8.2 Software configuration ..............8-19 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 8 CONTACTRON motor management PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 9: Introduction

    In addition, the module generates signals to detect the direction of rotation. Phase failures are detected and signaled. Continuous status monitoring with high scanning rates enables complete system protection, including motor protection. 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 10 Increase in Signaling threshold, performance, tool wear tool wear Performance when idling Time (t) Motor startup Tool positioning Milling process Drive shutdown Figure 1-1 Example for broken tool PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 11 Performance Lower performance threshold Time (t) Inrush suppression Delay time Continuous dry running with forced shutdown Performance Lower performance threshold Time (t) Figure 1-2 Example for dry running 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 12: About This User Manual

    6-1 Description of the software for parameterizing "CONTACTRON-DTM-IFS device the electronic motor management modules drivers" on page 7-1 Application examples for the products described "Application examples" on page 8-1 here PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 13: Emm 3

    I1 2 I1 1 I3 2 h 2 I3 1 I2 2 I2 1 Voltage measuring input Current measuring inputs via external current transformers Thermistor input EMM 3-.../500AC-IFS Figure 2-1 EMM 3-.../500AC...-IFS 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 14: Safety Regulations/Installation Notes

    In environment B (domestic applications), this device can cause undesirable radio interference; in such a case, the user may be required to implement appropriate measures. – The EMM 3- 24DC... can also be used in environment B (domestic applications). PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 15: Connection Notes

    Only connect conductors with the same conductor cross section to a terminal point. If you wish to monitor a 690 V network with EMM 3-.../500AC-IFS devices, the UT 4-MTDR/CVC 690/SET voltage transducer (Order No. 2901667) must be used. 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 16: Thermistor Input

    The TBUS DIN rail connector can only be used to supply the modules if 24 V DC devices are used. The EMM 3-.../500AC...-IFS modules can be mounted on a DIN rail. For detailed information about mounting/removal, please refer to "TBUS DIN rail connector" on page 5-1. PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 17: Connection Versions

    O U O O1 O2 O3 O4 Thermistor input Reverse running 1/L1 3/L2 5/L3 Separate switching module Forward running 2/T1 4/T2 6/T3 Figure 2-3 EMM 3-.../500AC-16-IFS for line currents up to 16 A 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 18 For currents > 16 A, use EMM 3-.../500AC-IFS modules. These require additional external current transformers. Appropriate PACT Analog current transformers can be found in the Phoenix Contact INTERFACE catalog. The basic insulation requirements are met by PACT current transformers. A selection guide can be found in 6 on page 6-1.
  • Page 19: Function

    LED (ERR). The device then enters the safe shutdown state. To exit this state (external error), error acknowledgment is required. All internal errors cannot be acknowledged and are stored in the Flash memory. 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 20 For certain errors, an automatic acknowledgment can be parameterized. Confirmation All unused outputs of the EMM are available for confirmations. The behavior of the reply outputs is specified by the parameterization. PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 21: Parameterization

    Star/delta Input IN1 Start/stop Input IN2 No function (logic operation on request) Input IN3 On-site control Input IN4 Reset Output O1 Mains contactor Output O2 Delta contactor Output O3 Star contactor 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 22: Technical Data

    EMM 3- 24DC/... EMM 3-230AC/... Thermistor input 1 ... 6 thermistors in series (PTC) For ATEX applications: 3 ... 6 thermistors Total cold resistance ≤ 1.5 kΩ Operate value ≤ 3.72 kΩ 2-10 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 23 40 ... 100 Hz Rated frequency according to IEC 60947-1 50 ... 60 Hz 50 ... 60 Hz Output power of external transformer ≥ 1.25 VA EMM internal resistance 0.02 Ω 2-11 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 24 Mounting Can be aligned without spacing Coordination type (EMM 3-.../500AC-16-IFS with 25 A Diazed) (short-circuit-proof on 10 kA network) Power station requirement DWR1300Zxx001/DD/70.80.8/830001:1985-08 Low voltage switching devices IEC 60947-4-2: 2007-09 2-12 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 25 PTB 10 ATEX 3024 Connection data EMM .../500AC-IFS EMM .../500AC-16-IFS Screw terminal blocks (solid/stranded) 0.14 ... 2.5 mm M3 thread, recommended tightening torque 0.5 Nm ... 0.6 Nm 26 - 14 AWG 2-13 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 26: Derating Curves

    EMM 3- 24DC/500AC-16-IFS Class 35-40 Ambient temperature [°C]  /  = Aligned with spacing of 20 mm  /  = Aligned without spacing Figure 2-5 Derating curves, EMM 3- 24DC/... 2-14 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 27: Emm 3-230Ac/500Ac-16-Ifs

    EMM 3-230AC/500AC-16-IFS Class 35-40 Ambient temperature [°C]  /  = Aligned with spacing of 20 mm  /  = Aligned without spacing Figure 2-6 Derating curves, EMM 3-230AC/... 2-15 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 28: Trigger Characteristics At 20°C

    22.6 25.8 12.5 13.5 15.3 17.4 10.2 11.5 12.9 10.3 For the EMM 3-.../500AC-16-IFS, blocking monitoring is activated with a motor current of 60 A or higher (see trigger characteristic). 2-16 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 29 = 16 A / Surge current 8 x I = 128 A / Class curve = Class 30 The EMM shuts the outputs down after 7.0 s as the measuring range is exceeded. 2-17 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 30: Safety Functions

    PFH - Probability of failure per hour 85 x 10 317 x 10 Table 2-6 Safety level for safe shutdown Standard Level IEC 61508-1 SIL 1 ISO 13849-1 PL b EN 954-1 Category 1 2-18 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 31 23.5 12.0 DC [%] - Diagnostic coverage 53.7 Table 2-8 Safety level for motor protection by thermistor Standard Level IEC 61508-1 SIL 1 Additional safety data is available on request. 2-19 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 32 CONTACTRON motor management 2-20 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 33: Ifs-Confstick-L Memory Block

    Wait until the DAT LED has gone out. Backup has been completed. Remove the IFS-CONFSTICK-L from the device. If an error is detected while saving or subsequently checking the data, the DAT and ERR LEDs flash simultaneously. 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 34: Loading The Device Configuration On The Emm

    The next time the supply voltage is switched on, the new configuration will be valid. If the configuration and parameterization data is invalid or an error has been detected, the DAT and ERR LEDs flash simultaneously and the data is not saved to the device. PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com...
  • Page 35: Technical Data

    Dimensions (width x height x depth) 16.5 mm x 6.5 mm x 39.5 mm Weight 4.5 g, approximately Ambient conditions Ambient temperature (operation) -25°C ... 60°C Ambient temperature (storage/transport) -25°C ... 60°C 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 36 CONTACTRON motor management PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 37: Em-Pb-Gateway-Ifs Profibus Module

    The PROFIBUS address is set using a button and/or a device (PC, memory stick, actuator) connected to the S-PORT as an option. The module does not provide PROFIBUS termination, an appropriate connector should be used for this, if required. 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 38 EM-PB gateway EM-PB gateway + EMM ... IFS 1 + EMM ... IFS up to EMM ... IFS 31, EMM ... IFS 32 Figure 4-2 PROFIBUS module for electronic motor management modules PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 39: Definition Of Terms

    Can be parameterized – Reads/writes data records Type files/GSD Device master data (GSD) contains DP slave descriptions in a uniform format. Using GSD simplifies the configuration of the master and DP slave. 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 40: Connection Notes

    Block diagram 4.2.3 TBUS DIN rail connector The EM-PB-GATEWAY-IFS can be mounted on a DIN rail. For detailed information about mounting/removal, please refer to "TBUS DIN rail connector" on page 5-1. PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 41: Status Leds

    Connected device has an internal error or is not present Flashing at 1.4 Hz (slow) Process error or error in the I/O of a device Flashing at 2.8 Hz (fast) PROFIBUS configuration and station structure do not match 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 42: S-Port Handling

    Press the button 1 on the EM-PB-GATEWAY-IFS for six seconds (6 s). The EM-PB-GATEWAY-IFS calculates the PROFIBUS address by adding the offset to the base address. The base address is set to 0 by default. PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 43: Ifs-Confstick

    EM-PB-GATEWAY-IFS PROFIBUS module Table 4-1 PROFIBUS address LED code Offset Default offset 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 44: Setting The Interface System Address

    3 and 4 until all the devices have been addressed. Press and hold down the button 1 for at least six seconds (6 s). All status LEDs light up briefly. PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 45 EM-PB-GATEWAY-IFS PROFIBUS module Table 4-2 INTERFACE system address Table 4-3 LED code IFSM address 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 46: Profibus Telegrams

    Representation range (default): -32512 ... 32512 Userdefined 2 (x 0.001) : 1000 Userdefined Scaling 2 (x 0.001) Representation range (default): -32512 ... 32512 IFS-Application 0: NON 1: ELR, EMM Byte order 0: Intel 1: Motorola 4-10 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 47: Structure Of The Diagnostic Telegram

    Checksum vendor area is invalid Reserved Undefined, unspecified internal error Modul state (High Byte) DPC Errors Stack error Checksum ROM is invalid Internal communication error Digital input error Reserved Reserved Reserved Reserved 4-11 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 48 Slave 30: error or missing Slave 29: error or missing Slave 28: error or missing Slave 27: error or missing Slave 26: error or missing Slave 25: error or missing 4-12 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 49 Slave 29: process or peripherie error Slave 28: process or peripherie error Slave 27: process or peripherie error Slave 26: process or peripherie error Slave 25: process or peripherie error 4-13 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 50 "IFSM-Bus-Error" "IFSM-Bit-Error" "IFSM-Cyclic-Data" "IFSM-Acyclic-Data" "IFSM-Invalid-Bus-Cycle-Time" Reserved Reserved Reserved Channel state 3 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Channel state 4 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 4-14 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 51: Configuration Telegram

    OUT process data Description O1: Digital output 1 O2: Digital output 2 O3: Digital output 3 O4: Digital output 4 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 4-15 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 52: Module Status

    Manufacturer area of EEPROM, FLASH faulty Configuration area of EEPROM, FLASH faulty Supply voltage monitoring, reference voltage monitoring Switching output monitoring (switching output overloaded) Reserved Configuration mode active Reserved Reserved Reserved Reserved Memory stick faulty 4-16 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 53: Station Status

    Device 13: Faulty, not present, serious internal error Device 14: Faulty, not present, serious internal error Device 15: Faulty, not present, serious internal error Device 16: Faulty, not present, serious internal error 4-17 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 54 Device 11: Process error, message Device 12: Process error, message Device 13: Process error, message Device 14: Process error, message Device 15: Process error, message Device 16: Process error, message 4-18 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 55 Device 27: Process error, message Device 28: Process error, message Device 29: Process error, message Device 30: Process error, message Device 31: Process error, message Device 32: Process error, message 4-19 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 56: Emm Objects

    Channel 1: Configuration area of EEPROM, FLASH Supply voltage monitoring, reference voltage monitoring Reserved Digital input monitoring Error acknowledgment faulty Channel 1: Logical program sequence monitoring faulty Reserved Channel 1: Return stack overflow 4-20 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 57 Mains symmetry monitoring Phase failure (UL1 - UL3) Mains failure (mains regeneration time) Mains synchronicity Limit switch left Limit switch right Execution time at switch-on moment Execution time at switch-off moment 4-21 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 58 10 Hz cycle: The signal is inverted every 50 ms Group message Group error message Drive control: Automatic / manual Simultaneous activation of left and right rotation IFSM bus error Fault in test mode 4-22 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 59 Interruption of motor line T1 Interruption of motor line T2 Interruption of motor line T3 Leaving the analog measuring range (EMM…5A) Thermistor short circuit Thermistor warning Thermistor overtemperature Thermistor wire break 4-23 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 60: Measured Values - Contactron Motor Manager Emm

    7530 (30000) +0.666667 m +333.33 m 0001 (1) 0000 -0.666667 m -333.33 m FFFF (-1) -30000 8AD0 (-30000) -21.6746 -10.837 -32512 8100 (-32512) < -21.6746 < -10.837 < -32512 8080 Underrange 4-24 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 61: Available Measured Values

    For power meters, operating hours counters, and operating cycle counters, an 8001h error code is not generated in the event of overrun (> 32512). The counter is reset instead. Additional status or measured values are available on request. 4-25 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 62: Technical Data

    0.2 mm - 2.5 mm (24 - 12 AWG) COMBICON plug-in screw connection Weight 180 g Data interface PROFIBUS Data rate 76.8 kbps 9.6 kbps ... 12 Mbps Connection method TBUS, S-port 9-pos. D-SUB 4-26 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 63 EM-PB-GATEWAY-IFS PROFIBUS module Ambient conditions Ambient temperature (operation) -35°C ... +50°C Ambient temperature (storage/transport) -35°C ... +80°C 4-27 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 64: Integration In Step 7

    Set INTERFACE system address See Section 4.2.7 on page 4-8 See Section 4.7.3 on page 4-30 Integrate into STEP 7 SW See Section 4.7.4 on page 4-38 Set byte order Figure 4-5 Flowchart 4-28 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 65: Downloading The Gsd File

    EM-PB-GATEWAY-IFS PROFIBUS module 4.7.2 Downloading the GSD file Access the Phoenix Contact online catalog (www.phoenixcontact.net/catalog) and search for "EM-PB-GATEWAY-IFS" or "2297620". Select "Downloads". Figure 4-6 Selecting "Downloads" in the online catalog Click on GSD file "PXC_0B51.gsd". Figure 4-7 Selecting the GSD file in the online catalog Read the General Terms and Conditions of Use.
  • Page 66: Integration In Step 7

    Start SIMATIC Manager Figure 4-10 SIMATIC Manager icon Create a new project. Figure 4-11 Creating a new project Assign a project name and click "OK". Figure 4-12 Saving the project name 4-30 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 67 Selecting the CPU The selected CPU is inserted in your project. Figure 4-14 Selected CPU Open the context menu of the inserted CPU. Click on "Open Object". Figure 4-15 Opening the object 4-31 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 68 CONTACTRON motor management The hardware configuration is displayed. Figure 4-16 Hardware configuration Close all application windows. Figure 4-17 Hardware configuration 10. Select "Options, Install New GSD...". Figure 4-18 Installing a GSD file 4-32 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 69 "Installation has been completed successfully" message 13. Open the context menu of the inserted CPU. 14. Click on "Open Object". Figure 4-20 Opening the object 15. Select "View, Catalog". Figure 4-21 Selecting the catalog 4-33 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 70 CONTACTRON motor management 16. The catalog window appears. Figure 4-22 Catalog window 17. Suitable devices must be inserted your project here. 4-34 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 71 Select "SIMATIC 300, RACK-300, Rail" and insert this in your project. Figure 4-23 Selecting the DIN rail Select "SIMATIC 300, CPU 315-2 DP, 6ES7-315-2AF03-0AB0, V1.2" and insert this in your project. Figure 4-24 Selecting the CPU 4-35 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 72 Click on "New" and assign a new name for the bus line. Figure 4-25 Bus line name Select "PROFIBUS DP, Additional Field Devices, Gateway". Now move the EM-PB-GATEWAY-IFS to your project. Figure 4-26 Selecting the gateway 4-36 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 73 EM-PB-GATEWAY-IFS in Section 4.2.6. Figure 4-27 Gateway properties You can now move the required GSD data to your project from under item "EM-PB-GATEWAY-IFS" in the catalog window. Figure 4-28 GSD data 4-37 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 74: Setting The Byte Order

    Big Endian (the high byte is saved first) Intel: Little Endian (the low byte is saved first) Example: Value "EMM: COS ϕ" Cos ϕ = 0.3661 Figure 4-30 Example: Value "EMM: COS ϕ" 4-38 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 75: Explanation Of Gsd Data

    EMM: Control (Device:7) 7 = IFS address 7 EMM: Control (Device:8) 8 = IFS address 8 EMM: Status EMM: Module State 1 EMM: Module State 2 EMM: Channel State 1 4-39 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 76 EMM: Operation time (right) EMM: Cycle (left) EMM: Cycle (right) EMM: P(L1) EMM: P(L2) EMM: Q(ALL) EMM: S(ALL) EMM: SQRT(3) * U(L1) EMM: SQRT(3) * U(L2) EMM: SQRT(3) * U(L3) 4-40 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 77: Example

    The following modules are used in this example: – SIMATIC S7-300 – EM-PB-GATEWAY-IFS – EMM 3- 24DC/500AC-16-IFS 4.7.6.1 Hardware structure PROFIBUS address: 4 PROFIBUS address: 2 IFS address: 2 IFS address: 1 Figure 4-31 Hardware structure 4-41 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 78 Display: Operating hours counter (right rotation) Display: Cycles (left rotation) Display: Cycles (right rotation) Display: Voltage L1 Display: Voltage L2 Display: Voltage L3 Display: Current L1 Display: Current L2 Display: Current L3 4-42 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 79 EM-PB-GATEWAY-IFS PROFIBUS module 4.7.6.3 Monitoring variables Figure 4-32 Opening the context menu of the EM-PB-GATEWAY-IFS Figure 4-33 Object properties of the EM-PB-GATEWAY-IFS 4-43 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 80 In the example screen, you can see that the real power (All) is 278 W. For each EM-PB-GATEWAY-IFS, a maximum of 32 words can be transferred during the cycle (66 ms). 4-44 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 81: Tbus Din Rail Connector

    A connection can be established between two DIN rail connectors using MINI COMBICON connectors: MC 1,5/5-ST-3,81 (female connector, 1803604); IMC 1,5/5-ST-3,81 (male connector, 1857919). The maximum cable length is 10 m. Use shielded cables. Figure 5-2 Mounting/removal 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 82: Technical Data

    Rated voltage 125 V Impulse voltage withstand level 2.5 kV Maximum load current Dimensions (width x height x depth) 30 mm x 20 mm x 37 mm Weight 5 g, approximately PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 83: Current Transformer Selection Guide

    This selection guide can be used to find a suitable current transformer for EMM... electronic motor management modules from Phoenix Contact. The tables refer to current transformers in the PACT MCR range from Phoenix Contact. You can also use current transformers from other manufacturers, which meet the requirements...
  • Page 84: Three-Phase Induction Motor At A Rotational Frequency Of 3000 Rpm

    PACT MCR...1250 PACT MCR...1000 PACT MCR...200 PACT MCR...125 PACT MCR...1500 PACT MCR...1000 PACT MCR...200 PACT MCR...150 PACT MCR...1600 PACT MCR...1250 PACT MCR...250 PACT MCR...200 PACT MCR...2000 PACT MCR...1500 PACT MCR...300 PACT MCR...250 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 85: Three-Phase Induction Motor At A Rotational Frequency Of 1500 Rpm

    PACT MCR...1000 PACT MCR...750 PACT MCR...150 PACT MCR...125 PACT MCR...1250 PACT MCR...1000 PACT MCR...200 PACT MCR...150 PACT MCR...1500 PACT MCR...1000 PACT MCR...200 PACT MCR...150 PACT MCR...1600 PACT MCR...1250 PACT MCR...250 PACT MCR...200 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 86: Three-Phase Induction Motor At A Rotational Frequency Of 1000 Rpm

    PACT MCR...600 PACT MCR...100 PACT MCR... 80 PACT MCR...1000 PACT MCR...750 PACT MCR...150 PACT MCR...125 PACT MCR...1250 PACT MCR...1000 PACT MCR...200 PACT MCR...150 PACT MCR...1500 PACT MCR...1250 PACT MCR...250 PACT MCR...200 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 87: Three-Phase Induction Motor At A Rotational Frequency Of 750 Rpm

    PACT MCR...500 PACT MCR...100 PACT MCR... 75 PACT MCR...800 PACT MCR...600 PACT MCR...125 PACT MCR... 80 PACT MCR...1250 PACT MCR...800 PACT MCR...150 PACT MCR...125 PACT MCR...1250 PACT MCR...1000 PACT MCR...200 PACT MCR...150 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 88: Recommended Restart Time

    Recommended restart time following bimetal response when using Ex e motors: Typical time constants within (-----) Motor size Figure 6-1 Recommended restart time A restart time of 120 minutes can be achieved with the CONTACTRON-DTM-IFS. PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 89: Contactron-Dtm-Ifs Device Drivers

    PROFIBUS DP controller boards, HART modems or gateway devices. The devices in the CONTACTRON EMM... product range (electronic motor management) product range from Phoenix Contact can be used to switch, measure, warn, protect, monitor, and evaluate. The electronic management module offers all the familiar advantages of real power monitoring.
  • Page 90: System Requirements

    MS Internet Explorer Version 6.0 or later Mozilla Firefox Version 3.5 or later Designation Description FDT container IFS-Conf AutomationXplorer+ CONTACTRON-DTM-IFS DTM devices for integrating the EMM module in the FDT container PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 91: Programming Adapter

    CONTACTRON-DTM-IFS device drivers 7.1.4 Programming adapter Designation Description Order No. IFS-USB-PROG-ADAPTER Programming adapter for configuring 2811271 Phoenix Contact INTERFACE modules with 12-pos. S-PORT interface 7.1.5 Configuration package Designation Description Order No. MM-CONF-SET The configuration package contains the following 2297992 components:...
  • Page 92: Connecting The Programming Adapter

    The programming adapter must not be used in potentially explosive areas. Do not use the programming adapter if you suspect that it is damaged. The adapter may only be used to program supported Phoenix Contact INTERFACE devices. Check the documentation for your device to see whether the programming adapter is compatible.
  • Page 93: Connection To The Pc

    On the device, connect the programming adapter to the 12-pos. S-PORT interface. Figure 7-3 Connection to the device NOTE: Potential damage to cables Position the programming adapter so that no strain is placed on the plug-in connection on the device. 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 94: Technical Data

    Ambient temperature (storage/transport) -40°C … +85°C, -40°F ... +185°F Humidity, no condensation 90% (25°C) Conformance with EMC Directive 2004/108/EC Noise immunity according to EN 61000-6-2 Noise emission according to EN 61000-6-4 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 95: Software Setup

    This calls the installation wizard, which guides you through the installation process. Follow the instructions in the installation program until it comes to selecting the software to be installed. Here you can decide whether you wish to use AutomationXplorer+ or IFS-Conf. 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 96: Uninstallation

    CONTACTRON motor management DTMs from various manufacturers can be integrated in AutomationXplorer+. Only Phoenix Contact DTMs can be integrated in IFS-Conf. IFS-Conf is used in all the following descriptions. Confirm the dialog box with "Next". Follow the instructions in the installation program. The installation program generates all the directories required for operation and copies the necessary files.
  • Page 97: Configuration

    For more detailed information about IFS-Conf, please refer to the online help. 7.3.3.1 Creating a user When IFS-Conf is started for the first time, you need to create a user. Figure 7-4 Starting the application for the first time 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 98 CONTACTRON motor management In the following example, an administrator with the name "EMM" is created. Figure 7-5 Creating a user 7-10 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 99 Transfer the CONTACTRON-DTM-IFS from the selection table to the current DTM catalog. To do this, proceed as follows: Select the CONTACTRON-DTM-IFS or several DTMs simultaneously and click on the ">>" button or transfer all the DTMs by clicking on "All >>". 7-11 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 100 DTMs at a later time, follow the same procedure. Figure 7-7 DTM catalog management Closing catalog Click on "Update Catalog and Close Window". management Catalog management is closed. 7-12 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 101 Figure 7-8 Topology Scan Wizard Establishing a connection When a device is found, the connection is established automatically and the "Observe" dialog box is opened. Figure 7-9 "Observe" dialog box 7-13 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 102 Show the DTM catalog via the "View, DTM Catalog" menu. Drag the required hardware from the "DTM Catalog" and drop it into the "Project Tree" or insert it by double-clicking. 7-14 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 103: Emm 3- Xx/500Ac/Xx-Ifs Module Parameter Menu

    Online connection activated DTM toolbar DTM catalog (hidden by default) Parameter menu Status bar Parameter list Buttons Figure 7-10 Activated online connection to the EMM 3- xx/500AC/xx-IFS module 7-15 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 104: Buttons In The Ifs-Conf Toolbar

    Offline comparison No function Settings... The settings dialog box is opened. Scan topology... A topology scan is started. Monitor... The monitoring dialog box is opened. Diagnostics... No function Info No function 7-16 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 105: Buttons In The Dtm Toolbar

    DTM In the event of technical queries regarding the parameterization of the EMM 3- xx/500AC/xx-IFS module, please have the details of the DTM used to hand ("About this DTM" button). 7-17 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 106: Status Bar

    A function test is being carried out Value limits Limits of the value range exceeded Maintenance Determined values are not consistent required Device OK Output signals are within the valid value range Diagnostics Diagnostics deactivated deactivated 7-18 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 107: Settings

    Clear assignment between the devices and data is required. 7.4.5 Settings The editing of a project involves the settings for a selected device. Clicking on the "Settings..." button in the IFS-Conf toolbar opens the "Settings" dialog box. 7-19 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 108 If the EMM is controlled via an IFS gateway you have to select "by IFS Gateway". Then input 3 at the EMM is used for activation of "on-site control" (see "Program side default setting of inputs and outputs" on page 7-28). 7-20 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 109 "Voltage transformer" configuration dialog box The following parameter data can be set: Parameter Selection value Interval Program side Voltage transformer – direct, no transformer direct, no transformer – 690 V AC (Order No. 2901667) 7-21 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 110 Amplitude transmission factor – Min: 1 0.01 – Max: 1000 "Current transformer selection guide" on page 6-1 contains an overview which you can use to find a suitable current transformer. 7-22 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 111 Max: 759 (EMM ... IFS) Delay time – Min: 0 – Max: 60000 Underrange (behavior) – Disabled – Disable drive – Disabled – Generate message Underrange (acknowledgment) – Automatic – Automatic – Manual 7-23 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 112 Min: 0 – Max: 60000 Mains voltage failure (behavior) – Disabled – Disable drive – Disabled – Generate message Mains voltage failure (acknowledg- – Automatic – Automatic ment) – Manual 7-24 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 113 – Automatic – Automatic – Manual Faulty rotating field (behavior) – Disabled – Disable drive – Disabled – Generate message Faulty rotating field (acknowledgment) – Automatic – Automatic – Manual 7-25 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 114 Selection value Interval Program side Symmetry-threshold – Min: 3 – Max: 100 Behavior – Disabled – Disable drive – Disabled – Generate message Acknowledgment – Automatic – Automatic – Manual 7-26 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 115 Interruption of motor line – Manual – Manual (acknowledgment) Motor current-symmetry (behavior) – Disabled – Disable drive – Disable drive – Generate message Motor current-symmetry – Manual – Manual (acknowledgment) 7-27 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 116 EMM so that on-site control can be implemented directly at the EMM. If the EMM...IFS is not connected to an EM-PB-GATEWAY-IFS, input 3 has no function. 7-28 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 117 0.01 A – Min. 0.3 A (for EMM...IFS) 0.3 A (for EMM...IFS) – Max: 4000 A (for EMM...IFS) Behavior – Disabled – Disable drive – Disable drive – Generate message 7-29 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 118 1.8 s Class 10 3.4 s Class 15 4.1 s Class 20 4.7 s Class 25 6.4 s Class 30 7.0 s Class 35 7.8 s Class 40 8.6 s 7-30 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 119 – Automatic – Automatic (acknowledgment) – Manual Tolerance time – Min: 0 – Max: 60000 Short To Ground Current – Calculated, at least 30% of the set 0.01 bimetal current 7-31 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 120 Wire break (acknowledgment) – Automatic – Manual – Manual Short circuit (behavior) – Disabled – Disable drive – Disabled – Generate message Short circuit (acknowledgment) – Automatic – Manual – Manual 7-32 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 121 CONTACTRON-DTM-IFS device drivers Parameter Selection value Interval Program side Pre-warning level (behavior) – Disabled – Disable drive – Disabled – Generate message Pre-warning level (acknowledgment) – Automatic – Automatic – Manual 7-33 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 122 – Generate message At Activation (Acknowledgment) – Manual – Manual At De-Activation (Behavior) – Disabled – Disable drive – Disabled – Generate message At De-Activation (Acknowledgment) – Manual – Manual 7-34 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 123 Manual – Manual (Acknowledgment) In case of activated state (Behavior) – Disabled – No restart – Disabled – Generate message In case of activated state – Manual – Manual (Acknowledgment) 7-35 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 124 – Disabled – Always – During right and left rotation – During right rotation – Disabled – During left rotation – On demand right rotation – On demand left rotation 7-36 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 125 – Standstill time – Standstill time last interval Trigger at – Overrange Overrange – Underrange Behavior – Disable drive Generate message – Generate message Acknowledgment – Automatic Automatic – Manual 7-37 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 126 CONTACTRON motor management Parameter Selection value Interval Program side Limit switch – – Left – Right 7-38 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 127 The following parameter data can be set: Parameter Selection value Interval Program side IFS-Bus error (behavior) – Disabled – Disable drive – Disable drive – Generate message IFS-Bus error (acknowledgment) – Automatic – Automatic – Manual 7-39 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 128: Online/Offline Parameters

    "Write to device". If you wish to proceed in the "Offline Parameter" dialog box, you must first click "Apply" or "OK" in the "Settings" dialog box. 7-40 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 129 The following parameter data can be set: Parameter Selection value Interval Program side From right to left rotation – Min: 1 – Max: 60000 From left to right rotation – Min: 1 – Max: 60000 7-41 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 130 Min: 0 of errors – Max: 60000 Delay until reversing – Min: 0 during left rotation – Max: 60000 Delay until reversing – Min: 0 during right rotation – Max: 60000 7-42 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 131 Max: 60000 Nominal current for – Min: 0 changing into delta 0.01 – Max: 160000 operation Change-over delay at – Min: 25 changing from star to delta – Max: 60000 operation 7-43 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 132 "General Settings" parameter dialog box The following parameter data can be set: Parameter Selection value Interval Program side Execution time – Min: 0 – Max: 60000 Response time – Min: 0 – Max: 60000 7-44 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 133 Start-up suppression time – Min: 0 – Max: 60000 Set point – Min: -5000000 – Max: 5000000 Hysteresis – Min: 0.1 – Max: 100 Delay time – Min: 0 – Max: 60000 7-45 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 134 Figure 7-33 shows an example of the real power curve for a pump where the real power remains below the lower performance threshold even after a time delay. This may be due to dry running. 7-46 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 135 Figure 7-34 shows an example of temporary dry running (air bubble in the system). For example, the upper performance threshold is reached in the event of a blockage. The performance level is reached again before the time delay has elapsed. 7-47 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 136 Enabled Mains voltage phase failure – Disabled – Disabled – Enabled Mains voltage symmetry – Disabled – Disabled monitoring – Enabled Faulty rotating field – Disabled – Disabled – Enabled 7-48 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 137 – Enabled Monitoring 8 – Disabled – Disabled – Enabled Execution time at activation – Disabled – Disabled – Enabled Execution time at – Disabled – Disabled deactivation – Enabled 7-49 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 138 – Enabled Response time at deactiva- – Disabled – Disabled tion state – Enabled Error Overcurrent – Disabled – Disabled – Enabled ShortToGround – Disabled – Disabled – Enabled 7-50 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 139: Writing The Configuration To The Device

    "invalid configuration" error state. To exit this error state, repeat the write process with a valid configuration and confirm it with "OK". Figure 7-36 Writing the configuration to the device 7-51 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 140: Monitoring Dialog Box

    Manual request – fast left rotation Left rotation Manual request – left rotation Stop Manual request – stop Right rotation Manual request – right rotation Fast right rotation Manual request – fast right rotation 7-52 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 141: Overview

    Display of total real power Frequency Display of mains frequency Cos Phi Display of total power factor Cos Phi – Operation time Display of operating time (data is saved internally on the device) hhhhhh:mm:ss 7-53 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 142: Online Values

    Display of total and phase-specific power factor Cos Phi – Current Display of phase-specific line currents Voltage Display of phase-specific nominal voltage values Line voltage Display of phase-specific line voltage values 7-54 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 143 (in the example: Real power, Real power L1, etc.). Clicking the button enlarges the area on the Y-axis defined by the two limit markers to fit the entire screen height. 7-55 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 144 Clicking the "Save" button calls the "Save As" dialog box. Enter the required file name here, according to Windows conventions. The curve file is automatically assigned the file extension *.sgl. Figure 7-40 "Save As" dialog box 7-56 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 145 CSV file. Figure 7-42 Export file dialog box The time is saved in the following format in the CSV file: hh:mm:ss,000. This should be noted when importing into Excel. 7-57 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 146: Counter

    Display of left rotation total cycles – Day counter left Display of left rotation day cycles – Right Display of right rotation total cycles – Day counter right Display of right rotation day cycles 7-58 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 147: Messages/Errors

    Monitoring 1 ... 8 A parameterized value of monitoring 1 ... 8 is outside its limits (see "Monitoring 1 ... 8" on page 7-36 and "Monitoring 1 ... 8" on page 7-45) 7-59 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 148 For EMM 3-xx/500AC-IFS only: If the measured value is greater than 6 A for more than 9 seconds: "Operational" area of application: Message is generated. "ATEX" area of application: Motor is shut down. 7-60 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 149: Application Examples

    1 should output a warning which is automatically acknowledged when the day counter is reset. 8.1.1 Hardware configuration 24 V Warning IN1 IN2 IN3 IN4 EMM 3-24DC/500AC-16-IFS L1 L2 L3 3~ Load Figure 8-1 Hardware configuration example 1 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 150: Software Configuration

    Manual Online Parameter Monitoring - Monitoring 1 Start-up suppression 0 x 10 ms time Set point 20 kWh Delay time 0 x 10 ms Outputs - Output 1 Monitoring 1 Enabled PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 151: Example 2 - Direct Starter For Pump Monitoring

    Output 4 should be used as the error message output (overrange and underrange). Set the motor current on the ELR H3… 8.2.1 Hardware configuration 24 V IN1 IN2 IN3 IN4 EMM 3-24DC/500AC-16-IFS ELR H3-SC-24VDC/500AC-9 Figure 8-2 Hardware configuration example 2 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 152: Software Configuration

    Generate message Acknowledgment Automatic Monitoring - Monitoring 4 Activation During right rotation Shutdown in the event of blockage Monitoring signal Effective power : total Trigger at Overrange Behavior Disable drive Acknowledgment Manual PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 153 200 x 10 ms Set point 620 W Delay time 200 x 10 ms Outputs - Output 3 Monitoring 1 Enabled Monitoring 3 Enabled Outputs - Output 4 Monitoring 2 Enabled Monitoring 4 Enabled 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 154: Example 3 - Direct Starter With Current Transformer

    S1/k IN1 IN2 IN3 IN4 S2/l S1/k EMM 3-24DC/500AC-IFS S2/l S1/k V1 V2 V3 O1 O2 O3 O4 S2/l 18,5 kW contactor Start / Stop Figure 8-3 Hardware configuration example 3 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 155: Software Configuration

    Monitoring - Monitoring 2 Activation During right and left rotation Shutdown in the event of overrange, e.g., filter blocked Monitoring signal Effective power : total Trigger at Overrange Behavior Disable drive Acknowledgment Manual 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 156 Feedback: Motor right rotation Enabled Feedback: Motor left rotation Enabled Outputs - Output 4 Monitoring 1 Enabled Monitoring 2 Enabled Thermistor overtemperature Enabled Thermistor short circuit Enabled Thermistor wire break Enabled PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 157: Example 4 - Reversing Starter In Potentially Explosive Areas (Atex)

    In this example, a motor is controlled in an EEx area in right/left mode. In addition to the normal reversing starter, EEx-relevant data must be set here. 8.4.1 Hardware configuration 24 V IN1 IN2 IN3 IN4 EMM 3-24DC/500AC-16-IFS separate switching module Figure 8-4 Hardware configuration example 4 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 158: Software Configuration

    Monitoring - Monitoring 2 Activation During right and left rotation Shutdown in the event of overrange Monitoring signal Effective power : total Trigger at Overrange Behavior Disable drive Acknowledgment Manual 8-10 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 159 Outputs - Output 3 Bimetal monitoring Enabled Outputs - Output 4 Monitoring 1 Enabled Monitoring 2 Enabled Thermistor overtemperature Enabled (optional) Thermistor wire break Enabled (optional) Thermistor short circuit Enabled (optional) 8-11 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 160: Example 5 - Star/Delta

    A1 A2 L1 L2 L3 A1 A2 L1 L2 L3 Mains contactor Star contactor Delta contactor T1 T2 T3 T1 T2 T3 T1 T2 T3 Figure 8-5 Hardware configuration example 5 8-12 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 161: Software Configuration

    Start-up suppression time 100 x 10 ms Set point 350 W Delay time 100 x 10 ms Outputs - Output 4 Bimetal monitoring Enabled Monitoring 1 Enabled Monitoring 2 Enabled 8-13 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 162: Example 6 - Star/Delta Lr

    L1 L2 L3 A1 A2 L1 L2 L3 Mains contactor left Mains contactor right Star contactor T1 T2 T3 T1 T2 T3 T1 T2 T3 Figure 8-6 Hardware configuration example 6 8-14 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 163: Software Configuration

    Set point 250 W Delay time 100 x 10 ms Monitoring - Monitoring 2 Start-up suppression time 100 x 10 ms Set point 350 W Delay time 100 x 10 ms 8-15 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 164: Example 7 - Reversing Starter With Connection To Profibus

    "Integration in STEP 7" on page 4-28. 8.7.1 Hardware configuration 24 V IN1 IN2 IN3 IN4 EM-PB-GATEWAY-IFS EMM 3-24DC/500AC-16-IFS TBUS- connector O1 O2 O3 O4 separate switching module Figure 8-7 Hardware configuration example 7 8-16 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 165: Software Configuration

    Feedback: Motor right rotation Enabled Feedback: Motor left rotation Enabled Outputs - Output 4 Monitoring 1 Enabled Monitoring 2 Enabled Thermistor overtemperature Enabled Thermistor short circuit Enabled Thermistor wire break Enabled 8-17 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 166: Example 8 - 690 V Reversing Starter With Voltage Transducer

    IN1 IN2 IN3 IN4 V1 V2 V3 S2/l S1/k EMM 3-24DC/500AC-IFS S2/l S1/k O1 O2 O3 O4 S2/l 690 V switching module Reverse running Forward running Figure 8-8 Hardware configuration example 8 8-18 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 167 Monitoring - Monitoring 2 Activation During right and left rotation Shutdown in the event of overrange Monitoring signal Effective power : total Trigger at Overrange Behavior Disable drive Acknowledgment Manual 8-19 104456_en_01 PHOENIX CONTACT RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...
  • Page 168 Feedback: Motor right Enabled rotation Feedback: Motor left rotation Enabled Outputs - Output 4 Monitoring 1 Enabled Monitoring 2 Enabled Thermistor overtemperature Enabled Thermistor short circuit Enabled Thermistor wire break Enabled 8-20 PHOENIX CONTACT 104456_en_01 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-793-Phoenix-Contact-2986122-Memory-Block-IFS-CONFSTICK.aspx...