Generator Ac Connection System - GE HOME GENERATOR SYSTEM 27000-30000 WATT Installation And Start-Up Manual

27000-30000 watt home generator system
Table of Contents

Advertisement

Available languages

Available languages

Generator ac connection system

A single-phase, three-wire AC connection system is used in
the home generator. The stator assembly consists of a pair
of stationary windings with two leads brought out of each
winding. The junction of leads T2 and T3 forms the neutral
lead, as shown schematically and as wiring diagram. A
complete schematic and wiring diagram can be found later
in this manual.
note: Neutral is not bonded to ground at generator.
When making connections, obey wire type and torque
specifications shown on the circuit breaker and neutral/
ground connector.
T2
T3
Circuit
Breaker
T4
T1
T4
T1
Neutral
N
Neutral
Line 1
Line 2
To Transfer Switch
Control
Water
Board
Heater
10 A
240 VAC
To Transfer Switch
Utility Fuse Connection
Neutral
120 V
120 V
240 V
Ground
G
Ground
10 A
17