If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
Calibrate Your Module for a ControlNet or an EtherNet/IP Network... . 29 Use DeviceNetManager Software to Calibrate Your Module ..... . 35 Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 4
..............47 Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, rok.auto/certifications Provides declarations of conformity, certificates, and other certification details.
These instructions let the adapter obtain input or output values and status from the module, and let you establish the modules mode of operation. Figure 2 shows the typical communication process. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
The current draw through the terminal base determines the wiring of the terminal base unit. Verify that the current draw does not exceed 10 A. ATTENTION: Total current draw through the terminal base unit is limited to 10 A. Separate power connections may be necessary. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 9
24V DC All modules that are powered by the same power supply must be analog modules in this configuration. The total current draw through any base unit must not be greater than 10 A. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 10
Chapter 1 Overview of FLEX I/O System and Thermocouple/mV Module Notes: Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
The same block transfer control file is used for both the read and write instructions for your module. A different block transfer control file is required for every module. A sample program segment with block transfer instructions is shown in Figure 4, and described as follows: Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
CONTROL: N13:20 DATA FILE: LENGTH: CONTINUOUS: PLC-2 Programming The FLEX I/O analog modules are not recommended for use with PLC-2® family programmable controllers due to the number of digits needed for high resolution. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
0…2315 °C (32…4199 °F) 0…23150 (320…41990) 0.1 °C (0.1 °F) Type E –270…+1000 °C (-454…+1832 °F) –2700…+1000 (-4540…+18320) 0.1 °C (0.1 °F) Type J –210…+1200 °C (-346…+2192 °F) –2100…+12000 (-3460…+21920) 0.1 °C (0.1 °F) Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
The module uses up to 11 words of input Modules image and up to 3 words of output image. Each word is composed of 16 bits. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 15
Write Word 2 Thermocouple 7 Type Thermocouple 6 Type Thermocouple 5 Type Thermocouple 4 Type CK = Calibration clock CH = Calibration high Where: CL = Calibration low FDF = Fixed digit filter bit Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 16
Calibration mask – The channel or channels to be calibrated have the correct mask bit set. The bit 8 corresponds to the 08…15 (10…17) channel 0, bit 9 corresponds to the channel 1, and so on. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 17
Channel 5 Thermocouple Type (see write word 1, bits 00…03) Write Word 2 08…11 (10…13) Channel 6 Thermocouple Type (see write word 1, bits 00…03) 12…15 (14…17) Channel 7 Thermocouple Type (see write word 1, bits 00…03) Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 18
Chapter 3 Write Configuration to Your Module and Read Status from Your Module with a Remote I/O Adapter Notes: Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
I/O Module Fault bits – 1 status bit for each slot • Node Address Changed bit – 1 bit • I/O State bit– 1 bit I/O Module Fault bits Bit: 10...15 Not Used I/O State bit Node Address Changed bit Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
The selection influences the A/D output data rate, thus affecting system throughput. The number of channels included in each input scan also affects system throughput. Mapping Data into the The FLEX I/O thermocouple module data table mapping is shown in Figure Image Table Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 21
Write Word 2 Thermocouple 7 Type Thermocouple 6 Type Thermocouple 5 Type Thermocouple 4 Type CK = Calibration clock CH = Calibration high Where: CL = Calibration low FDF = Fixed digit filter bit Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 22
Calibration mask – The channel or channels to be calibrated have the correct mask bit set. The bit 8 corresponds to the 08…15 (10…17) channel 0, bit 9 corresponds to the channel 1, and so on. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
You can reduce the write words to 0, thus eliminating the configuration setting and unused words. And you can reduce the read words to 10 by eliminating the calibration status words. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 24
Chapter 4 Communication and I/O Image Table Mapping with the DeviceNet Adapter Notes: Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
If you use a sensor other than a thermocouple, disconnect the lead wires at the sensor and tie together for this measurement. Reconnect after measurement. d. After measurement, remove the ohmmeter. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
To let the internal temperature of the module stabilize, energize the module for at least 40 minutes before you start calibration. Module calibration consists of: • Applying a reference voltage to the desired inputs Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 27
BTW = Block transfer write BTR = Block transfer read CB = Calibration bad CD = Calibration done CR = Calibration range CD = 1 CK = Calibration clock CH = Calibration high CL = Calibration low Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 28
CK = Calibration clock CB = Calibration bad CH = Calibration high Where: CD = Calibration done CL = Calibration low CR = Calibration range FDF = Fixed digit filter bit BS = Bad structure Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
During calibration the module stores the calibration data for two set points referred to as offset and gain. The offset calibration is taken with input 0.000 mV and the gain calibration is done with 75.000 mV. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 30
CalibrationOutOfRange = 0 Set CalibrationClock = 0 Set CalibrationClock = 0 GainOffsetCalibration = 0 CalibrationDone = 0 CalibrationDone = 0 Clear the corresponding bits in the calibration mask. Legend: MR = Module reconfigure Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 31
+24V DC Power Terminals 34, 35, 50, and 51 For 1794-TB3: Terminals 34…51 (1) Terminals 36, 37, 38 and 47, 48, 49 are cold junction compensator connections. (2) Terminals 39…46 are chassis ground. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 32
3. Right-click on the tag name given in the Message Control field and declare it as a New MR_msg. 4. Select the button next to MR_msg. The Message Configuration - MR_msg dialog appears. 5. From the Message Type dropdown list, select Module Reconfigure. 6. Select Communication tab. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 33
If CalibrationMaskChN is 1, this channel (Channel N) is calibrated. If CalibrationMaskChN is 0, this channel (Channel N) is not calibrated. 4. Set the GainOffsetCalibration bit to 0 and send a ModuleReconfigure. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 34
10. If individually calibrating the channels, perform the Step 1…Step 8 again for offset calibration on any additional channels that you want to calibrate. 11. Set all CalibrationMaskChN bits to 0. Send a ModuleReconfigure. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
3. Select the Slot, which contains your thermocouple module in Module Configuration. For example, in the following screen, the thermocouple input module is in Slot 0. You must select Slot 0. The following dialog appears: 4. Select Calibration... to get to the calibration screen. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
2. Under Channel Selection, select the checkboxes for channels that you want to calibrate. 3. Under Channel Type, select the Gain Calibration option. Then select Start Calibration. 4. When calibration is complete, you see a notification indicating Gain Calibration Successful in the Calibration Status area. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 37
Configuration screen. Select Save to Flex I/O or Save to File... to save the configuration. If you attempt to close without saving your configuration information by selecting the Close option, you are prompted to save the changes. Select Yes to continue. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 38
Chapter 5 Calibrate Your Module Notes: Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
±0.34 ±0.61 ±0.68 ±1.22 ±0.13 ±0.23 ±0.26 ±0.46 ±0.19 ±0.30 ±0.37 ±0.62 ±12 µV ±12 µV ±24 µV/°C ±24 µV/°F Note: The filter is enabled by setting bit 02 in write word 0. Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
Page 46
Appendix A Resolution Curves, Worst Case Accuracy, Error Due to Open Circuit Current, and Worst Case Repeatability Notes: Rockwell Automation Publication 1794-UM007B-EN-P - August 2024...
At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. Allen-Bradley, DeviceNetManager, expanding human possibility, FactoryTalk, FLEX, FLEX I/O-XT, PLC-2, PLC-3, PLC-5, Rockwell Automation, Studio 5000 Logix Designer, and TechConnect are trademarks of Rockwell Automation, Inc.
Need help?
Do you have a question about the Allen-Bradley 1794-IT8 and is the answer not in the manual?
Questions and answers