Chapter 5 Parameters|VFD-S Series
Group 9 Communication Parameters
Pr.
Communication
9-00
Address
9-01 Transmission Speed
Transmission Fault
9-02
Treatment
9-03 Time-out Detection
Communication
9-04
Protocol
Group A PID Parameters
Pr.
A-00
Input terminal for PID Feedback
A-01
Gain over PID Detection value
A-02
Proportional Gain (P)
A-03
Integral Time (I)
A-04
Derivative Control (D)
A-05
Upper Bound for Integral Control
A-06
Primary Delay Filter Time
A-07
PID Output Freq. Limit
A-08
Feedback Signal Detection Time
5-10
Explanation
Explanation
Settings
d1 to d254
d0: Baud Rate 4800 bps
d1: Baud Rate 9600 bps
d2: Baud Rate 19200 bps
d3: Baud Rate 38400 bps
d0: Warn and Keep Operating
d1: Warn and Ramp to Stop
d2: Warn and Coast to Stop
d3: Keep Operating without Warning
d0: Disable
d1 to d20: time setting (1 sec
increment)
d0: 7,N,2 (Modbus, ASCII)
d1: 7,E,1 (Modbus, ASCII)
d2: 7,O,1 (Modbus, ASCII)
d3: 8,N,2 (Modbus, ASCII)
d4: 8,E,1 (Modbus, ASCII)
d5: 8,O,1 (Modbus, ASCII)
d6: 8,N,2 (Modbus, RTU)
d7: 8,E,1 (Modbus, RTU)
d8: 8,O,1 (Modbus, RTU)
Settings
d0: Disable PID function
d1: Negative PID feedback from
external terminal (AVI) 0 to
+10V
d2: Negative PID feedback from
external terminal (ACI) 4 to
20mA
d3: Positive PID feedback from
external terminal (AVI) 0 to
+10V
d4: Positive PID feedback from
external terminal (ACI) 4 to
20mA
d0 to d999
d0 to d999
d0 to d999
d0 to d100
d0 to d100%
d0 to d999
d0 to d110%
d0.0 to d650 seconds
Revision August 2008, SE09, SW V2.61
Factory
NOTE
Setting
d1
d1
d0
d0
d0
Factory
NOTE
Setting
d0
d100
d100
d100
d0
d100
d0
d100
d0.0