Warning
Please read this instruction sheet carefully before use.
In order to prevent electric shock, DO NOT touch the terminals or conduct any maintenance while the power is on.
DO NOT open the PLC. Only qualified personnel or Delta staff is allowed to conduct any internal electrical work
on the PLC.
DVP04PT-S is an OPEN-TYPE device and certified to meet IEC 61131-2 (UL 508) safety requirements when
installed in an enclosure.
DVP04PT-S must be kept under the environment away from high temperatures, high humidity, exceessive vibration,
corrosive gases, liquids, airborne dust, and metallic particles.
DO NOT apply AC power to any of the input/output terminals, or it may damage DVP04PT-S.
Make sure that the DVP04PT-S is properly grounded
, to prevent any electromagnetic noise.
Please keep the wires as short as possible when connecting RTD to PLC and keep power lead as far away as
possible from I/O wires to prevent noise interference.
Introduction
Model Explanation & Peripherals
Thank you for choosing Delta DVP series PLC. DVP04PT-S is able to receive 4 points of platinum
temperature sensors (PT 100 3-WIRE 100 3850 PPM/°C (DIN 43760 JIS C1604-1989)) and convert
them into 14-bit digital signals. Besides, through FROM/TO instructions in DVP Slim series MPU program,
the data in DVP04PT-S can be read and written. There are 49 16-bit control registers (CR) in
DVP04PT-S.
The system version of DVP04PT-S can be updated via RS-485 communication. The power unit is
separate from it and is small in size and easy to install.
DVP04PT-S displays temperatures in both Celsius (resolution: 0.1° C) and Fahrenheit (resolution:
0.18° C).
Product Profile & Outline
4
5
3.4
1
25.20
6
3.00
60.00
60.00
3.00
7
11
L+
C
L-
H
I+
1
FG
L+
8
L-
C
H
I+
2
10
12
FG
14
●
L+
C
L-
9
H
13
90.00
I+
3
FG
L+
2
L-
C
H
I+
4
3
FG
●
3
4.00
Unit: mm
1. Status indicator (POWER, RUN and ERROR)
8. Extension port
2. Model name
9. Extension clip
3. DIN rail clip
10. DIN rail (35mm)
4. I/O terminals
11. RS-485 communication port
5. I/O point indicator
12. Extension clip
6. Mounting holes
13. DC power input
7. Specification label
14. Extension port
External Wiring
1mA
PT100
Shielded*1
CH1
L+
L-
I -
1mA
FG
AG
PT100
Shielded*1
CH4
L+
L-
I -
FG
AG
*2
terminal of
power module
*3
DC/ DC
24+
System
AG
24-
Converter
Grounding
Class 3 Grounding
(100
of less)
Note 1: Use only the wires that are packed with the temperature sensor (PT 100) for analog input and separate from other
power line or any wire that may cause noise. Please use 3-wire for PT 100.
Note 2: Terminal FG is grounded for noise suppression.
Note 3: Please connect
power supply module terminal and
DVP-04PT-S temperature measurement module
terminal to system earth ground.
Warning: DO NOT connect wires to the No Connection
terminals.
Specifications
Temperature
Celsius (° C)
measurement module
Power supply voltage
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
Analog input channel
4 channels per module
Sensors type
3- WIRE PT 100 3850 PPM/° C (DIN 43760 JIS C1604-1989)
Current excitation
1mA
Temperature input
-200° C ~ 600° C
range
Digital conversion
K-2,000 ~ K6,000
range
Resolution
14 bits (0.1° C)
14 bits (0.18° F)
Overall accuracy
±0.5% of full scale of 25° C (77° F), ±1% of full scale during 0 ~ 55° C (32 ~ 131° F).
Response time
200ms × channels
Isolation between digital and analog circuitry. There is no isolation between
Isolation method
channels.
Digital data format
2's complement of 16-bit, (13 significant bits).
Average function
Yes (CR#2 ~ CR#5 may be set and the range is K1 ~ K4,095)
Self diagnostic function
Yes
ENGLISH
Modbus ASCII or RTU Mode. Communication baud rate 4,800/9,600/19,200/38,400/
Communication mode
57,600/115,200. For ASCII mode, date format is 7 bits, even, 1 stop bit (7, E, 1),
(RS-485)
while RTU mode, date format is 8 bits, even, 1 stop bit (8, E, 1). RS-485 is disabled
when the DVP04PT-S is connected in series with an MPU.
Connection to a
If DVP04PT-S modules are connected to MPU, the modules are numbered from 0 -
DVP-PLC MPU in
7. 0 is the closest and 7 is the furthest to the MPU. 8 modules is the max and they
series
do not occupy any digital I/O points of the MPU.
Others
Power supply
Maximum power
2W at 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), supplied by external power
consumption
Environment
1. Operation: 0° C ~ 55° C (temperature), 50 ~ 95% (humidity), pollution degree 2
Operation/storage
2. Storage: -25° C ~ 70° C (temperature), 5 ~ 95% (humidity)
Vibration/shock
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
immunity
CR (Control Register)
DVP04PT-S temperature measurement module
RS-485
CR
parameter
Latched
Register name
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#
address
○
System used, data length is 8 bits (b7 ~ b0).
#0
H'4064
R
Model type
DVP-04PT model code = H'8A.
○
#2
H'4066
R/W CH1 average number
○
Number piece of readings used for the calculation of
#3
H'4067
R/W CH2 average number
"average" temperature on channels CH1 ~ CH4.
○
#4
H'4068
R/W CH3 average number
Setting range is K1 ~ K4,095 and default setting is K10.
○
#5
H'4069
R/W CH4 average number
#6
H'406A
╳
R
CH1 average degrees (°C)
Average degrees for channels CH1 ~ CH4.
(Unit: 0.1 degrees C). Temperature is calculated by
#7
H'406B
╳
R
CH2 average degrees (°C)
90.00
averaging multiple pieces temperature readings. Example: If
#8
H'406C
╳
R
CH3 average degrees (°C)
CR#2 is 10, the temperature in CR#6 will be the average of
the last 10 readings on CH1.
#9
H'406D
╳
R
CH4 average degrees (°C)
#12
H'4070
╳
R
CH1 average degrees (°F)
Average degrees for channels CH1 ~ CH4.
#13
H'4071
╳
R
CH2 average degrees (°F)
(Unit: 0.1 degrees F). Temperature is calculated by averaging
multiple pieces temperature readings. Example: If CR#2 is
#14
H'4072
╳
R
CH3 average degrees (°F)
10, the temperature in CR#12 will be the average of the last
10 readings on CH1.
#15
H'4073
R
CH4 average degrees (°F)
╳
#18
H'4076
R
Present temperature of CH1 (°C)
╳
#19
H'4077
R
Present temperature of CH2 (°C)
╳
Present temperature of channels CH1 ~ CH4.
(Unit: 0.1 degrees C).
#20
H'4078
R
Present temperature of CH3 (°C)
╳
#21
H'4079
R
Present temperature of CH4 (°C)
╳
DVP04PT-S temperature measurement module
RS-485
CR
parameter
Latched
Register name
#
address
DVP04PT-S
#24
H'407C
R
Present temperature of CH1 (°F)
╳
#25
H'407D
R
Present temperature of CH2 (°F)
╳
L+
L-
#26
H'407E
R
Present temperature of CH3 (°F)
I-
╳
FG
L+
#27
H'407F
R
Present temperature of CH4 (°F)
╳
L-
I-
FG
#30
H'4082
R
Error status
╳
L+
L-
CR#30 is the error code register. Refer to the chart below.
I-
FG
Error description
Content
b15 ~ b8
L+
L-
I-
Power source abnormal
K1 (H'1)
5V
FG
Wiring
to empty external
K2 (H'2)
AG
contact
+15V
Setting mode error
K4 (H'4)
-15V
Offset/Gain error
K8 (H'8)
Reserved
Hardware malfunction
K16 (H'10)
Digital range error
K32 (H'20)
Average times setting error
K64 (H'40)
Instruction error
K128 (H'80)
Note: Each error code will have corresponding bit (b0 ~ b7). Two or more errors may happen at the same time. 0 means normal
and 1 means having error.
○
#31
H'4083
R/W Communication address setting
Fahrenheit (° F)
○
Communication
baud
#32
H'4084
R/W
setting
-328° F ~ 1112° F
K-3,280 ~ K11,120
○
#33
H'4085
R/W Reset to default setting
DVP04PT-S temperature measurement module
RS-485
CR
parameter
Latched
Register name
#
address
○
#34
H'4086
R
Software version
#35 ~ #48
System used
Symbols:
means latched.
╳
means not latched.
(Support when using RS-485 communication, not support when connecting with MPU)
R means read data by using FROM instruction or RS-485.
W means write data by using TO instruction or RS-485.
The corresponding parameters address H'4064 ~ H'4086 of CR#0 ~ CR#34 are provided for users to
read/write data via RS-485 communication.
A. Communication baud rate: 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps.
B. Communication format: ASCII mode is 7 bits, even bit, 1 stop bit (7, E, 1). Communication format of RTU
mode is 8 bits, even bit, 1 stop bit (8, E, 1).
C. Function code: 03'H - read data from register. 06'H - write one word to register. 10'H - write multiple
Explanation
words to registers.
Temperature/Digital Curve
Temperature mode (Celsius):
Dig ital Output
+6,000
+3,000
-200
C
Temperature mode (Fahrenheit):
Dig ital O utp ut
+11 ,12 0
+5,5 60
- 328
F
Explanation
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Present temperature of channels CH1 ~ CH4.
(OPEN TYPE)
(Unit: 0.1 degrees F).
Data register stores the error status. Refer to the error code
chart for details.
b7
b6
b5
b4
b3
b2
b1
b0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
1
0
說 明 及 週 邊 裝 置
0
0
0
0
0
1
0
0
0
0
0
0
1
0
0
0
0
0
0
1
0
0
0
0
100 3850 PPM/
0
0
1
0
0
0
0
0
SA/SX/SC/SV
0
1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
DVP04PT-S
產 品 外 觀 及 各 部 介 紹
RS-485 communication address.
Setting range is 01 ~ 254 and default setting is K1.
Communication baud rate (4,800, 9,600, 19,200, 38,400,
57,600 and 115,200 bps).
1
25.20
3.00
b0: 4,800 bps (bit/sec).
b1: 9,600 bps (bit/sec). (default setting)
b2: 19,200 bps (bit/sec).
b3: 38,400 bps (bit/sec).
rate
b4: 57600 bps (bit/sec).
90.00
b5: 115,200 bps (bit/sec).
2
b6 ~ b13: Reserved.
3
b14: switch between low bit and high bit of CRC code (RTU
mode only).
b15: RTU mode.
4.00
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Definition of ERR
1.
CH4
CH3
CH2
CH1
LED
2.
Example: Setting of CH1
3. DIN
1. b0: Reserved.
2. b1: Reserved.
4.
3. b2: Set to 1 and PLC will be reset to default settings.
5.
Definition of ERR LED: b12~b15=1111 (default settings)
/
6.
1. b12 corresponds to CH1: when b12=1, scale exceeds the
range, ERR LED flashes.
7.
Explanation
外 部 配 線
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
PT100
2. b13 corresponds to CH2: when b13=1, scale exceeds the
range, ERR LED flashes.
3. b14 corresponds to CH3: when b14=1, scale exceeds the
range, ERR LED flashes.
4. b15 corresponds to CH4: when b15=1, scale exceeds the
range, ERR LED flashes.
PT100
Display the software version in hexadecimal.
Example: H'010A = version 1.0A.
接 至 電 源 模
組 之 端
第 三 種 接 地
(
接 地 抗 阻
1
2
3
(04PT)
Temperature Input
+60 0
C
-2,0 00
Temp er atu re Input
+1,112
F
- 3,2 80
/
(
)
/
DVP
DVP04PT-S
4
(PT 100 3
°C
(DIN 43760 JIS C1604-1989))
14
DVP-PLC SS/
FROM/TO
49
CR (Control Register)
16 bits
RS-485
0.1°C
0.18°F
4
5
3.4
6
60.00
60.00
3.00
7
11
L+
L-
C
H
I+
1
FG
8
L+
C
L-
I+
H
10
12
2
FG
14
●
L+
C
9
L-
H
13
90.00
I+
3
FG
L+
L-
C
H
I+
4
3
FG
●
mm
8.
/
/
9.
10. DIN
(35mm)
11. RS-485
12.
/
13.
14.
/
1mA
隔 離 線
*1
CH1
DVP04PT-S
L+
L-
I-
L+
1mA
L-
FG
AG
I-
FG
L+
隔 離 線
*1
L-
CH4
I-
L+
FG
L-
I-
L+
FG
L-
AG
I-
FG
*2
5V
L+
L-
I-
AG
FG
+15V
DC/ DC
*3
24+
AG
系 統 接 地 點
24-
轉 換 器
-15V
100
以 下
)
PT 100
PT 100
3
FG
DVP04PT-S
(°C)
(°F)
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
4
/
3-WIRE PT100 3850 PPM/°C (DIN 43760 JIS C1604-1989)
1mA
-200°C ~ 600°C
-328°F ~ 1112°F
K-2,000 ~ K6,000
K-3,280 ~ K11,120
14 bits (0.1°C)
14 bits (0.18°F)
±0.5%
(25°C, 77°F)
±1%
(0 ~ 55°C, 32 ~ 131°F)
200ms ×
16
13 bits
(CR#2 ~ CR#5
K1 ~ K4,095)