ENGLISH Thank you for choosing Delta DVP series PLC. DVP04PT-S is able to receive 4 points of platinum temperature sensors (PT 100 3-WIRE 100 3850 PPM/°C (DIN 43760 JIS C1604-1989)) and convert them into 14-bit digital signals. Besides, through FROM/TO instructions in DVP Slim series MPU program, the data in DVP04PT-S can be read and written.
PT100. Note2: Terminal FG is grounded for noise suppression. Note3: Please connect power supply module terminal and DVP04PT-S temperature measurement module terminal to system earth ground. Warning: DO NOT connect wires to the No Connection terminals. Electrical Specifications DVP04PT-S Power supply voltage 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Digital data format 2’s complement of 16-bit Average function Yes (CR#2 ~ CR#5) Self diagnostic function Communication mode Yes (CR#32). RS-485 is disabled when the DVP04PT-S is (RS-485) connected in series with an MPU. Control Register CR# Address Save Register content...
Page 5
CR# Address Save Register content Description For ASCII mode, date format is 7 bits, even, 1 stop bit (7, E, 1), while RTU mode, date format is 8 bits, even, 1 stop bit (8, E, 1). b0: 4,800 bps (bit/sec). b1: 9,600 bps (bit/sec).
Page 6
3. When CR#29 is set to H’5678, CR#0 ~ CR#34 can be used for PID settings in DVP04PT-S V3.08 and versions above. PID Mode Content Description CR#0 Model name CR#17 CH4 K CR#2 Output % at CH1 CR#19 CH1 K...
Page 11
CR#17 CH4 K CR#27 CH4 K CR#19 CH1 K CR#28 Run/Stop & Auto turning CR#20 CH2 K CR#29 (H’5678) CR#21 CH3 K CR#30 CR#22 CH4 K CR#31 CH1 CR#24 CH1 K CR#32 CH2 CR#25 CH2 K CR#33 CH3 CR#26 CH3 K CR#34 CH4 +6,000 +11,120...
Page 16
CR#17 CH4 K CR#27 CH4 K CR#19 CH1 K CR#28 Run/Stop & Auto turning CR#20 CH2 K CR#29 (H’5678) CR#21 CH3 K CR#30 CR#22 CH4 K CR#31 CH1 CR#24 CH1 K CR#32 CH2 CR#25 CH2 K CR#33 CH3 CR#26 CH3 K CR#34 CH4 +6,000 +11,120...