Warning
Please read this instruction carefully before use.
DO NOT tough any terminal when the power is switched on. Switch off the power before wiring.
DVP06AD-S is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device
(e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all
the wiring again before switching on the power.
DO NOT touch any internal circuit in 1 minute after the power is switched off.
Make sure the groud terminal
is correctly grounded in order to prevent electromagnetic interference.
Introduction
Model Explanation & Peripherals
Thank you for choosing Delta DVP series. The analog signal input module DVP06AD-S is able to receive 6
points of external analog signal inputs (both in voltage and current) and convert the signals into 14-bit
digital ones. It is able to read and write the data in the module through FROM/TO instructions given by the
program of DVP-PLC SS/SA/SX/SC/SV series MPU. There are 49 16-bit control registers in the module.
The user can select voltage or current output by wiring. Range of voltage output: 10V DC (resolution:
1.25mV). Range of current output: 20mA (resolution: 5µA).
Product Profile & Outline
1. POWER, ERROR, A/D indicator
60.00
3
4
1
2. DIN rail clip
25.20
60.00
3.40
5
3. Terminals
4. Extension unit/module mounting hole
6
9
12
8
5. Nameplate
10
6. Extension unit/module connection port
7
7. Extension unit/module fixing clip
11
2
8. DIN rail (35mm)
2
9. RS-485 communication port
10. Extension unit/module fixing notch
3.00
11. Power input port
Unit: mm
12. Extension unit/module connection port
External Wiring
Voltage input
DVP06AD-S
-10V~+10V
CH1
104.7K
CH1
V+
250
*4
I+
100K
V+
COM
I+
COM
Shielding cable*1
V+
AG
I+
COM
V+
Current input
CH6
104.7K
I+
CH6
-20mA~+20mA
V+
COM
*2
250
I+
100K
V+
COM
I+
COM
Shielding cable*1
AG
V+
I+
COM
Connected to
V+
I+
terminal
+15V
COM
of the power module
DC/DC
24+
*3
AG
24-
Coverter
-15V
System grounding
Eart h
(
100
or less)
*1: When performing analog input, please isolate other power wirings.
*2: When connecting to current signals, please make sure to short-circuit "V+" and "I+" terminals.
*3: Please connect the
terminal on both the power module and DVP06AD-S to the system earth point and ground the
system contact or connect it to the cover of power distribution cabinet.
*4: If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the
wiring to 0.1 ~ 0.47µF 25V capacitor.
Note: DO NOT wire empty terminals
Specifications
Functions
Analog/Digital
Voltage input
(6A/D) module
Power supply voltage
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
Analog input channel
6 channels/module
Range of analog input
±10V
Range of digital
±8,000
conversion
Resolution
14 bits (1
=1.25mV)
LSB
Input impedance
200K
or more
±0.5% when in full scale (25° C, 77° F)
Overall accuracy
±1% when in full scale in the range of 0 ~ 55° C, 32 ~ 131° F
Response time
3ms × the number of channels
Isolation
Isolation between digital area and analog area. No isolation among channels.
Range of absolute input
±15V
Digital data format
13 significant bits out of 16 bits are available; in 2's complement.
Average function
Yes. Available for setting up in CR#2 ~ CR#7; range: K1 ~ K20.
Self-diagnosis
Upper and lower bound detection/channel
ASCII/RTU mode.
Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200
Communication mode
ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1)
(RS-485)
RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1)
RS-485 cannot be used when connected to PLC MPU in series.
The modules are numbered from 0 to 7 automatically by their distance from MPU.
When connected to
Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O
DVP-PLC MPU in series
points.
Others
Power supply
Max. rated power
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2W, supplied by external power.
consumption
Environment
Operation: 0° C ~ 55° C (temperature); 50 ~ 95% (humidity); pollution degree 2.
Operation/storage
Storage: -25° C ~70° C (temperature); 5 ~ 95% (humidity).
Vibration/shock
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC
immunity
68-2-27 (TEST Ea)
Installation & Wiring
ENGLISH
Mounting Arrangements and Wiring Notes
How to install DIN rail
DVP-PLC can be secured to a cabinet by using the DIN rail of
35mm in height and 7.5mm in depth. When mounting PLC to
DIN rail, be sure to use the end bracket to stop any side-to-side
movement of PLC and reduce the chance of wires being loosen.
A small retaining clip is at the bottom of PLC. To secure PLC to
DIN rail, place the clip onto the rail and gently push it up. To
remove it, pull the retaining clip down and gently remove PLC
from DIN rail, as shown in the figure.
Wiring
1. Use 22-16AWG (1.5mm) single or multiple core wire on I/O wiring terminals. The
22-16AWG
specification of the terminal is shown in the figure on the left. The PLC terminal
screws shall be tightened to 1.95 kg-cm (1.7 in-lbs).
2. DO NOT place the I/O signal wires and power supply wire in the same wiring duct.
< 1.5 mm
3. Use 60/75 ºC copper wires only.
Control Registers
RS-485
CR
parameter
Latched
Register content
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#
address
Set by the system. Data length: 8 bits (b7 ~ b0).
#0
H'4000
R
Model name
DVP06AD-S model code=H'C8.
Reserved
CH6
Input mode: Default=H'0000.
Mode 0: Voltage input (-10V ~ +10V)
#1
H'4001
R/W Input mode setting
Mode 1: Voltage input (-5V ~ +10V)
Mode 2: Current input (-12mA ~ +20mA)
Mode 3: Current input (-20mA ~ +20mA)
CR#1: The working mode of the 6 channels in the analog input module. There are 4 modes for each channel which can
be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0=00) and CH2: mode 1 (b5 ~ b3=01),
CH3: mode 2 (b8 ~ b6=10), CH4: mode 3 (b11 ~ b9=11), CH5: mode 0 (b11 ~ b9=00), CH6: mode 1 (b11 ~ b9=01), CR#1
has to be set as H'04EA and the higher bits (b12 ~ b15) have to be reserved. Default value=H'0000.
#2
H'4002
R/W
CH2
CH1 ~ CH6
#3
H'4003
R/W
CH4
Average times setting
#4
H'4004
R/W
CH6
CR#2 ~ CR#4: Range of settings in CH1 ~ CH6: K1 ~ K20. The settings of average times of the signals at CH1 ~ CH6.
Range: K1 ~ K20. For example, if the average time at CH1 is to be set as K10 and CH2 as K18, CR#2 has to be set as
H'120A. CR#3 ~ 4 apply the same rule. The default setting of each channel=K10. Default settings of CR#2 ~ CR#4 are all
H'0A0A.
#6
H'4006
R
CH1 input average
#7
H'4007
R
CH2 input average
#8
H'4008
R
CH3 input average
Average of input signals at CH1 ~ CH6
#9
H'4009
R
CH4 input average
#10 H'400A
R
CH5 input average
#11
H'400B
R
CH6 input average
CR#6 ~ CR#11: The average of the signals at CH1~CH6 obtained from the settings in CR#2~CR#4. For example, if the
settings in CR#2~CR#4 is 10, the content in CR#6~CR#11 will be the average of the most recent 10 signals at CH1~CH6.
RS-485
CR
parameter
Latched
Register content
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#
address
#12 H'400C
R
CH1 input present value
#13 H'400D
R
CH2 input present value
#14 H'400E
R
CH3 input present value
#15
H'400F
R
CH4 input present value
#16
H'4010
R
CH5 input present value
#17
H'4011
R
CH6 input present value
#18
H'4012
R/W Adjusted OFFSET value of CH1
#19
H'4013
R/W Adjusted OFFSET value of CH2
#20
H'4014
R/W Adjusted OFFSET value of CH3
Current input
#21
H'4015
R/W Adjusted OFFSET value of CH4
#22
H'4016
R/W Adjusted OFFSET value of CH5
#23
H'4017
R/W Adjusted OFFSET value of CH6
#24
H'4018
R/W Adjusted GAIN value of CH1
±20mA
#25
H'4019
R/W Adjusted GAIN value of CH2
#26 H'401A
R/W Adjusted GAIN value of CH3
±4,000
#27 H'401B
R/W Adjusted GAIN value of CH4
13 bits (1
=5µA)
#28 H'401C
R/W Adjusted GAIN value of CH5
LSB
250
#29 H'401D
R/W Adjusted GAIN value of CH6
CR#18 ~ CR#29: Please note that: GAIN value – OFFSET value=+800
(current) When GAIN – OFFSET is small (steep oblique), the resolution of input signal will be finer and variation on the
digital value will be greater. When GAIN – OFFSET is big (gradual oblique), the resolution of input signal will be rougher
and variation on the digital value will be smaller.
#30 H'401E
R
Error status
±32mA
CR #30: Error status value (see the table below):
Error status
Content
b15 ~ b8
Abnormal power supply
K1 (H'1)
Incorrect mode setting
K4 (H'4)
Offset/Gain error
K8 (H'8)
Hardware malfunction
K16 (H'10)
Reserved
Abnormal digital range
K32 (H'20)
Incorrect average times setting
K64 (H'40)
Instruction error
K128 (H'80)
Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors
occurring at the same time. 0=normal; 1=error
#31
H'401F
R/W Communication address setting
Communication speed (baud
#32
H'4020
R/W
rate) setting
Return to default setting;
#33
H'4021
R/W
OFFSET/GAIN tuning
Please install PLC in an
authorization
enclosure with sufficient
space around it to allow
heat dissipation as shown
in the figure.
CR for input mode, setting of average times, OFFSET value and GAIN value will be reset after returning to default settings.
D
#34
H'4022
R
Firmware version
D
D
DVP
MP
D
#35 ~ #48
For system use
D > 50 mm
Symbols:
: Latched (when written in through RS-485 communication).
: Non-latched.
R: Able to read data by FROM instruction or RS-485 communication.
W: Able to write data by TO instruction or RS-485 communication.
LSB (Least Significant Bit): 1. For voltage input: 1
=10V/8,000=1.25mV.
LSB
2. For current input: 1
=20mA/4,000=5µA.
LSB
CR#0 ~ CR#34: The corresponding parameter addresses H'4000 ~ H'4022 are for users to read/write data
by RS-485 communication. When using RS-485, the user has to separate the module with MPU first.
a. Function codes: 03'H (read register data); 06'H (write 1 word datum to register); 10'H (write many words
data to register).
b. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written
by MPU through TO/DTO instruction.
Adjusting A/D Conversion Curve
CH5
CH4
CH3
CH2
CH1
Voltage input mode:
+
0 0
CR#1 mode 0:
GAIN=5V (4,000
M o de 0
CR#1 mode 1:
GAIN=6V (4,800
+ 4, 000
M od e 1
The voltage input value when the digital input value=4,000.
GAIN:
0
5V
6 V
Range: -3,200
-10V
-6V
2V
10V
OFFSET
GAIN
The voltage output value when the digital input value=0.
OFFSET:
-4,
00
0
Range: -4,000
Vol tage in put
GAIN - OFFSET: Range: +800
- 8,
00
0
CH1
Current input mode:
CH3
CR#1 mode 2:
GAIN=20mA (4,000
CH5
Mode 3
+ 4,000
Mode 2
CR#1 mode 3:
GAIN=20mA (4,000
The current input value when the digital input value=+4,000.
GAIN:
-20mA
-12mA
Range: -3,200
0
4mA
20mA
OFFSET
GAIN
The current input value when the digital input value=0.
OFFSET:
Range: -4,000
current input
GAIN - OFFSET: Range: +800
- 4,
00
0
The user can adjust the OFFSET/GAIN curves according to the actual needs by changing the OFFSET value
(CR#18 ~ CR#23) and GAIN value (CR#24 ~ CR#29).
注 意 事 項
(OPEN TYPE)
Present value of input signals at CH1 ~ CH6
OFFSET settings at CH1 ~ CH6. Default=K0; Unit: LSB.
產 品 簡 介
When voltage input, range: K-4,000
~ K4,000
.
LSB
LSB
When current input, range: K-4,000
~ K4,000
.
LSB
LSB
Please refer to this instruction sheet when setting OFFSET and
GAIN.
說 明 及 週 邊 裝 置
DVP
GAIN settings at CH1 ~ CH6. Default=K4,000; Unit: LSB.
When voltage input, range: K-3,200
~ K16,000
.
LSB
LSB
When current input, range: K-3,200
~ K10,400
.
LSB
LSB
Please refer to this instruction sheet when setting OFFSET and
±20mA (
5µA)
GAIN.
~ +12,000
(voltage) or +800
~ +6,400
產 品 外 觀 及 各 部 介 紹
LSB
LSB
LSB
LSB
3
1
25.20
60.00
Register for storing all error status.
See the table of error status for more information.
b7
b6
b5
b4
b3
b2
b1
b0
0
0
0
0
0
0
0
1
2
0
0
0
0
0
1
0
0
0
0
0
0
1
0
0
0
3.00
0
0
0
1
0
0
0
0
0
0
1
0
0
0
0
0
0
1
0
0
0
0
0
0
外 部 配 線
1
0
0
0
0
0
0
0
電 壓 輸 入
-10V~+10V
For setting RS-485 communication address.
Range: 01 ~ 254. Default=K1.
隔 離 線
For setting up RS-485 communication speed: 4,800/ 9,600/
電 流 輸 入
19,200/ 38,400/ 57,600/ 115,200bps. ASCII data format: 7-bit,
-20mA~ +20mA
even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1
stop bit (8, E, 1).
b0: 4,800 bps. b1: 9,600 bps (default).
隔 離 線
b2: 19,200 bps. b3: 38,400 bps.
接 至 電 源 模
b4: 57,600 bps. b5: 115,200 bps.
組 之 端
*3
b6 ~ b13: Reserved.
系 統 接 地 點
b14: High/low bit exchange of CRC checksum (only valid in
RTU mode).
接 地
(
接 地 阻 抗
100
b15: Switch between ASCII/RTU mode.
Return to default
CH6
CH5
CH4
CH3
CH2
CH1
1
Take the setting of CH1 for example:
2
1. b0: Switch for upper/lower bound alarm on the input value for
3
the channel. 0=disabled; 1=enabled (default).
2. b1: OFFSET/GAIN tuning. 0=forbidden; 1=allowed (default).
4
3. When b12 ~ b15=1, all values in CH1 ~ CH6 will return to
default settings. b12 ~ b15 will return to 0 automatically after
the setting is completed.
規 格
Displaying the current firmware version in hex, e.g. version
1.00 is indicated as H'0100.
功 能 規 格
/
(6A/D)
). OFFSET=0V (0
).
LSB
LSB
). OFFSET=2V (1,600
).
LSB
LSB
~ +16,000
.
LSB
LSB
~ +4,000
.
LSB
LSB
(RS-485)
~ +12,000
.
LSB
LSB
). OFFSET=4mA (800
).
LSB
LSB
DVP-PLC
). OFFSET=0mA (0
).
LSB
LSB
其 他 規 格
~ +10,400
.
LSB
LSB
~ +4,000
.
LSB
LSB
~ +6,400
.
LSB
LSB
/
/
/
( :
)
/
DVP06AD-S
6
14
DVP-PLC SS/SA/SX/SC/SV
FROM/TO
49
CR (Control Register)
16 bits
±10V DC (
1.25mV)
1.
60.00
4
2. DIN
3.40
5
3.
4.
/
6
9
12
5.
8
10
6.
/
7
7.
/
11
2
8. DIN
(35mm)
9. RS-485
10.
/
11.
尺 寸 單 位 :
m m
12.
/
CH1
104.7K
CH1
DVP06AD-S
V+
250
*4
I+
100K
COM
V+
I+
* 1
CO M
AG
V+
I+
CO M
V+
CH6
104.7K
I+
CH6
V+
CO M
*2
250
I+
100K
V+
COM
I+
CO M
V+
* 1
AG
I+
CO M
V+
I+
CO M
+15V
DC/DC
24+
AG
24-
轉 換 器
-15V
以 下
)
V+
I+
DVP06AD-S
0.1 ~ 0.47µF 25V
(Voltage input)
(Current input)
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
6
/
±10V
±20mA
±8,000
±4,000
14 bits (1LSB=1.25mV)
13 bits (1LSB=5µA)
200K
250
±0.5%
(25°C, 77°F)
±1%
(0 ~ 55°C, 32 ~ 131°F)
3ms ×
±15V
±32mA
16
13 bits
(CR#2 ~ CR#7
K1 ~ K20)
/
ASCII/RTU
(4,800/9,600/19,200/38,400/57,600
/115,200) ASCII
7 bits
1 stop bit (7, E, 1) RTU
8 bits
1 stop bit (8, E, 1)
PLC
RS-485
0
7
8
I/O
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2W,
0 C ~ 55 C (
) 50 ~ 95% (
)
2
-25 C ~ 70 C (
) 5 ~ 95%
IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)

Advertisement

loading

Summary of Contents for Delta Electronics Network Device DVP06AD-S

  • Page 1 *1: When performing analog input, please isolate other power wirings. *2: When connecting to current signals, please make sure to short-circuit “V+” and “I+” terminals. *3: Please connect the system contact or connect it to the cover of power distribution cabinet. *4: If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the wiring to 0.1 ~ 0.47µF 25V capacitor.
  • Page 2 RS-485 安 裝 及 配 線 盤 內 安 裝 及 配 線 H’4021 35mm CR#33 H’4022 D > 50 mm #35 ~ #48 22-16AWG (1.5mm) 22-16AWG 1.95 kg-cm (1.7Ib-in) < 1.5mm 60/75°C LSB (Least Significant Bit) 控 制 暫 存 器 CR#0 ~ CR#34 RS-485 b15 b14 b13 b12 b11 b10 b9...